ASBQA report, High School for Leadership & [name], 90 Trinity

Machine-extracted title · confidence 38%

ATC IAQ report for High School for Leadership & [name], Trinity Place, April 2002.

NYC-WTC_000394850–000394853
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 26, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Con^enp^ation

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the ; AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Ninety-four (94) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children..

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext # 211 or 212.

Sincerely, A TC ASSOCL4 T£S INC. Reviewed by;

James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002918751

NYC-WTC_000394853

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394853Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394734

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000291988

ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.

Similar indexed content

Compare copies and versions →