NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, High School for Leadership & [name], Apr 2002

Machine-extracted title · confidence 36%

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

NYC-WTC_000394787–000394790
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19, 2002 Indoor Air Quality Assessment - Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty eighteen (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 82.7°F to 95.1 °F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature range was 84.1 °F to 87.2 °F.

Relative Humidity

The relative humidity indoors ranged from 62.1 percent to 66.3 percent. All of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 63.6 to 65.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 509 ppm to 1100 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was601 ppm. Tlierefore, the maximum acceptable level of CO2 at this location was 1301 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

, Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 61 pg/m- with an average 23 pg/m^- All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/nP 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) measurement was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 22 pg/m^ to 68 pg/m^ with an average of 45 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC1OO_OO2918656

NYC-WTC_000394789

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394789Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394783

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000292020

ATC IAQ measurements collected June 24, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000394768

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

Compare copies and versions →