Mr Bernard P Orlan February 27, 2002 Indoor Air Quality Assessment Page 3 II S of Economics and Finance (M833) ATC Protect No 15-19125-0290
Real-Time Environmental Measurements
ATC collected eighty' (80) sets of real-time environmental measurements consisting of seventy'- mne (79) in the school building and one (1) outdoors The basement of the school was not surveyed because it was not accessible to the public Field data sheets are found in the Attachment Readings began at 3 31 PM and concluded after 6 18 PM The results are described below
Temperature
Indoor dry bulb temperature measurements ranged from 64 1°F to 79 6°F Three (3) of the measurements were below and forty-three (43) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions) The outdoor temperature was 55 1°F
Relative Humidity
The relative humidity indoors ranged from 28 0 percent to 45 9 percent Twenty-two (22) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort The outdoor relative humidity was 37 8 percent
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 450 ppm to 1178 ppm Only one (1) of the measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 453 ppm Therefore, the maximum acceptable level of CO2 at this location was 1153 ppm (background level + 700 ppm) The highest reading was recorded in Cafeteria at around 4 17PM Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-4 ppm These concentrations were below the NP/iAQS/ASHRAE guideline of 9 ppm The outdoor CO concentration was 4 ppm
Respirable Particulates (PM2 5/
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 32 pg/m^ with an average 8 pg/m^ None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration was 58 pg/m^ to 63 pg/m^
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average
CONFIDENTIAL, CITY_21MC100_003459410 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000257029
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000257035
IV notes on IAQ measurements collected for BOE program, Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256872
ATC report on indoor air quality measurements at a NYC high school site, conducted Feb 7, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297790
ATC IAQ report for Feb 13, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297826
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000257031
Indoor air quality measurements conducted at the referenced school; Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297808
ATC indoor air measurements report for February 14, 2002 at the school.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297874
ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297757
ATC quality report for IAQ measurements at a NYC high school in Feb 2002.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297663
Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.
10 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189753
Cover letter and report summary for indoor air quality measurements collected at a school on February 27, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297681
Indoor air quality report for the school, Feb 6, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297686
Report of IAQ measurements collected Feb 8, 2002 at the referenced New York City school.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000297826
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189753
Cover letter and report summary for indoor air quality measurements collected at a school on February 27, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297757
ATC quality report for IAQ measurements at a NYC high school in Feb 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297808
ATC indoor air measurements report for February 14, 2002 at the school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297790
ATC IAQ report for Feb 13, 2002 at the referenced school.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295895
March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000257035
IV notes on IAQ measurements collected for BOE program, Feb 2002.
Similar indexed content
NYC-WTC_000256872
ATC report on indoor air quality measurements at a NYC high school site, conducted Feb 7, 2002.
Similar indexed content
ATC IAQ report for Feb 13, 2002 at the referenced school.
Similar indexed content
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000257031
Indoor air quality measurements conducted at the referenced school; Feb 2002.
Similar indexed content