Indoor air quality report, M833, Feb 2002

Machine-extracted title · confidence 49%

Indoor air quality measurements at HS of Economics and Finance, Feb 2002.

NYC-WTC_000257027–000257030
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan February 27, 2002 Indoor Air Quality Assessment Page 2 H S of Economics and Finance (M833) ATCProiectNo 15-19125-0290 time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy

The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in cuiTent indoor air quality control activities

EVALUATION CRITERIA

CuiTently, there are no regulatory standards for indoor air quality in non-mdustrial buildings, such as offices and schools For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditiomng Engineers (ASHRAE), Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992), Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA)

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PARAMETER ; rARGEl LEVEL I (LA:, f Vr r ■ > ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS)____________ Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2 5) of air (p.g/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer 73-79°F at 50% RH ASHRAE 55 Winter 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = Ameiican Industrial Hygiene Association

CONFIDENTIAL, CITY_21MC1OO_OO34594O9 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000257028

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000257028Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297790

ATC IAQ report for Feb 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297826

ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →