Machine-extracted title · confidence 42%

TRC sampling report and assessment of dust in NYC Law Department server room, July 2003.

NYC-WTC_000246513–000246515
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

r Customer-Focused Solutions August 25, 2003

Anthony Johnson New York City Law Department 100 Church Street New York, NY 10007

Re: Additional Assessment of Fourth Floor Server Room, 100 Church Street, New York, New York TRC Project # 35052-0000-00019

Dear Mr Johnson;

Per your request, TRC Engineers, Inc. (TRC) performed additional sampling and evaluation of environmental conditions within the New York City Law Department (NYCLD) Server Room located on the 4**' floor at 100 Church Street. The intent of the additional assessment was to collect surface dust samples in the Server room to compare to the results presented in the RJLee Group, Inc. (RJL) report dated June 27, 2003, and to collect air samples in the space. Nazar Agahan of TRC performed sampling on July 17, 2003. Samples were hand delivered to EMSL Analytical, Inc. (EMSL) an independent New York State ELAP accredited laboratory (Number 11506) for analysis.

Asbestos Air Sampling: Two (2) asbestos area air samples were collected in the server room located on the 4* floor. These samples were collected under normal occupied conditions with two (2) 36-inch diameter industrial fans operating during the sampling period. Results of asbestos area air samples are presented in Attachment 1. Area air samples were analysed by. Transmission Electron Microscopy (TEM) following EPA 40 CFR Part 763 Final Rule (AHERA) Method.

Both samples taken in the 4* server room were found to be below the analjdical detection limit of the method (i.e. none detected).

Asbestos Surface Dust Sampling: Six (6) surface dust samples were collected from various areas of the server room following American Society for Testing and Materials (ASTM) Test Method D5755-95 Microvacuum Sampling and Indirect Analysis (Filter Sample Analysis) of Dust by Transmission Electron Microscopy (TEM) for Asbestos Structure Number Concentration, These included samples taken from the 12x12 grey floor tile, top of light fixture, top of computer, top of table, top of ventilation supply duct and from the top of drop in ceiling tiles. All samples were sent to EMSL for TEM analysis.

The sample results, presented in Attachment 1, indicate that five (5) of the six (6) samples collected were found to be below the analytical detection limit (i.e. none detected). One sample (NA071703ASBMV04) resulted in a concentration slightly above

1430 Broadway, 10th Floor • New York, New York 10018 Telephone 212-221-7822 • Fax 21 2-221-7840

CITY_21 MCI 00_014585137

NYC-WTC_000246513

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000246513Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000243532

EIA report for 100 Church Street preparation by TRC Engineers.

Similar indexed content

Compare copies and versions →