machine-extracted · confidence unavailable · Check page ↗TRC sampling report and assessment of dust in NYC Law Department server room, July 2003.
NYC-WTC_000246513–000246515OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
r Customer-Focused Solutions August 25, 2003
Anthony Johnson New York City Law Department 100 Church Street New York, NY 10007
Re: Additional Assessment of Fourth Floor Server Room, 100 Church Street, New York, New York TRC Project # 35052-0000-00019
Dear Mr Johnson;
Per your request, TRC Engineers, Inc. (TRC) performed additional sampling and evaluation of environmental conditions within the New York City Law Department (NYCLD) Server Room located on the 4**' floor at 100 Church Street. The intent of the additional assessment was to collect surface dust samples in the Server room to compare to the results presented in the RJLee Group, Inc. (RJL) report dated June 27, 2003, and to collect air samples in the space. Nazar Agahan of TRC performed sampling on July 17, 2003. Samples were hand delivered to EMSL Analytical, Inc. (EMSL) an independent New York State ELAP accredited laboratory (Number 11506) for analysis.
Asbestos Air Sampling: Two (2) asbestos area air samples were collected in the server room located on the 4* floor. These samples were collected under normal occupied conditions with two (2) 36-inch diameter industrial fans operating during the sampling period. Results of asbestos area air samples are presented in Attachment 1. Area air samples were analysed by. Transmission Electron Microscopy (TEM) following EPA 40 CFR Part 763 Final Rule (AHERA) Method.
Both samples taken in the 4* server room were found to be below the analjdical detection limit of the method (i.e. none detected).
Asbestos Surface Dust Sampling: Six (6) surface dust samples were collected from various areas of the server room following American Society for Testing and Materials (ASTM) Test Method D5755-95 Microvacuum Sampling and Indirect Analysis (Filter Sample Analysis) of Dust by Transmission Electron Microscopy (TEM) for Asbestos Structure Number Concentration, These included samples taken from the 12x12 grey floor tile, top of light fixture, top of computer, top of table, top of ventilation supply duct and from the top of drop in ceiling tiles. All samples were sent to EMSL for TEM analysis.
The sample results, presented in Attachment 1, indicate that five (5) of the six (6) samples collected were found to be below the analytical detection limit (i.e. none detected). One sample (NA071703ASBMV04) resulted in a concentration slightly above
1430 Broadway, 10th Floor • New York, New York 10018 Telephone 212-221-7822 • Fax 21 2-221-7840
CITY_21 MCI 00_014585137
NYC-WTC_000246513
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
No available related records indexed in this group.
NYC-WTC_000416996
Ambient air sampling and TEM analysis referenced for a New York building; dates include March 7, 2002.
4 shared non-person entities · similarity 0.952
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000149537
Instructions and sections for collecting sample location data from a specific building interior.
3 shared non-person entities · similarity 0.950
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243532
EIA report for 100 Church Street preparation by TRC Engineers.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243806
Environmental assessment for 100 Church Street prepared by TRC Engineers.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243668
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000120322
Report containing asbestos sampling data and analytical results for 1 Peck Slip dated October 3, 2001.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243703
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243565
EIA report for Law Department project at 100 Church Street by TRC.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000176247
Comprehensive environmental assessment report prepared by TRC Engineers for the New York City Law Department.
6 shared non-person entities · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000318672
Asbestos micro-vacuum sampling report for Office Equipment area, 40 Worth Street/4th Floor, Jan 7, 2003.
6 shared non-person entities · similarity 0.948
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000120940
Document tracking environmental samples collected from Building #100 at 345 South End Avenue on October 22, 2001.
3 shared non-person entities · 1 shared topics · similarity 0.948
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106116
Laboratory report detailing asbestos analysis using PLM, PCM, and TEM methods for bulk samples and air at 270 Broadway.
3 shared non-person entities · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000177286
Memo describing additional environmental sampling for dust and air conducted in July 2003 at the Law Department.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000246457
TRC report: assessment of suspect ACM in 2nd floor areas during renovation planning.
Similarity score 0.972 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000354038
Asbestos micro-vacuum sampling for NYC Mayor's Office of Operations; sites at Church and Worth Streets; TRC.
Similarity score 0.970 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000318672
Asbestos micro-vacuum sampling report for Office Equipment area, 40 Worth Street/4th Floor, Jan 7, 2003.
Similarity score 0.968 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236042
A cleaning verification report for the twentieth floor of 100 Church Street prepared by TRC Engineers for the New York City Law Department.
Similarity score 0.968 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000436063
Vacuum sampling results and procedures for 100 Church Street site investigation, January 2003.
Similarity score 0.967 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000416996
Ambient air sampling and TEM analysis referenced for a New York building; dates include March 7, 2002.
Similar indexed content
Instructions and sections for collecting sample location data from a specific building interior.
Similar indexed content
EIA report for 100 Church Street preparation by TRC Engineers.
Similar indexed content
NYC-WTC_000243806
Environmental assessment for 100 Church Street prepared by TRC Engineers.
Similar indexed content
NYC-WTC_000243668
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
Similar indexed content