NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Report providing indoor air quality measurements collected at a New York City Department of Education school to verify acceptable air levels.
NYC-WTC_000238685–000238689OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan August 28, 2002 Indoor Air Quality Assessment Page 4 P.S. 130 M ATC Project No. 15-19125-0345
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
The TVOCs indoor concentrations ranged from 0.1 to 0.2 ppm. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was not occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines. 2. Thirty-nine (39) of the indoor measurements were above the range of 73 to79 ’F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. One (1) of the indoor measurement for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 430 ppm. The highest reading was measured in room 304 with 21 occupants at 9:55 AM. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the forty-eight (48) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CONFIDENTIAL, CITY_21MC1OO_OO343O321 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000238688
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238877
Letter and report on indoor air quality measurements collected at P.S. 130M to verify acceptable air quality levels.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238806
Report of indoor air quality measurements collected at DeSoto School to verify acceptable air quality levels.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175150
Letter and report from ATC Associates regarding indoor air quality measurements collected at DeSoto School in August 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238877
Letter and report on indoor air quality measurements collected at P.S. 130M to verify acceptable air quality levels.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328522
Indoor air quality IAQ report for Dr. [name] at J.H.S. 131M; August 22, 2002 measurements.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000317091
IAQ memo documenting measurements at DeSoto School (PS 130M) in Aug 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similar indexed content
NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
Similar indexed content
NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similar indexed content
NYC-WTC_000238877
Letter and report on indoor air quality measurements collected at P.S. 130M to verify acceptable air quality levels.
Similar indexed content
NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
Similar indexed content