Mr. Bernard P. Orlan August 28, 2002
Indoor Air Quality Assessment Page 4
J.H.S. 131 M ATC Project No. 15-19125-0346
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs indoor concentrations ranged from 0.1 to 0.2 ppm. These concentrations were below
the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines.
2. Forty (40) of the indoor measurements were above the range of 73 to79 °F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading was measured in the basement office with 9 occupants at 2:46 PM. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source
of CO2 indoors is occupant respiration.
5. Two (2) of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-
hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic
diameter. Eight (8) of the forty-seven (47) instantaneous indoor readings were above the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic
people and children. All of the outdoor measurements for PM2.5 were below the NPAAQS
of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals such as asthmatic people and children.