NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan August 28, 2002
Indoor Air Quality Assessment Page 4
P.S. 130 M ATC Project No. 15-19125-0345
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcentration
The TVOCs indoor concentrations ranged from 0.1 to 0.2 ppm. These concentrations were below
the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• ■ The interior of the building appeared clean and free of dust and debris;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines.
2. Thirty-nine (39) of the indoor measurements were above the range of 73 to79 "F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer
season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. One (1) of the indoor measurement for CO2 was above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
outdoor (background) CO2 concentration was 430 ppm. The highest reading was measured
in room 304 with 21 occupants at 9:55 AM. Carbon dioxide measurements are used as an
indicator of available outdoor air. The primary source of CO2 indoors is occupant
respiration.
5. None of the indoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
Eight (8) of the forty-eight (48) instantaneous indoor readings were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people
and children. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals such as asthmatic people and children.
CONFIDENTIAL, CITY_2IMCl00_003430729
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000175234
OCR can misread numbers and units. Confirm readings against the page image before using them.