Mr. Bernard P. Orlan August 28, 2002 Indoor Air Quality Assessment Page 3 P.S. 130 M ____________________________ ATC Proiect No. 15-19125-034.5 Real-Time Environmental Measurements
ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-eight (48) in the school building and two (2) outdoors. All floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 74 to 84.4 ’F. Thirty-nine (39) of the indoor measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 78.8 to 79.2 °F.
Relative Humidity
The relative humidity indoors ranged from 40.5 percent to 52 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 44.5 to 48.2 percent.
CmRonD^ioxide Concentration
Carbon dioxide concentrations indoors ranged from 456 ppm to 1270 ppm. One (1) of the indoor measurement for CO? was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 430 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1130 ppm (background level + 700 ppm). The highest reading was measured in room 304 with 21 occupants at 9:55 AM. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 2 ppm for all readings
Respirable Particulates (PM2.5)
Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 45 pg/m^ with an average 32 pg/m-T None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the forty-eight (48) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 24 pg/m3 to 26 pg/m^ with an average of 25 pg/m3. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CONFIDENTIAL, CITY_21MC1OO_OO343O32O SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000238687
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238877
Letter and report on indoor air quality measurements collected at P.S. 130M to verify acceptable air quality levels.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238806
Report of indoor air quality measurements collected at DeSoto School to verify acceptable air quality levels.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175150
Letter and report from ATC Associates regarding indoor air quality measurements collected at DeSoto School in August 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similar indexed content
NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
Similar indexed content
NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similar indexed content
NYC-WTC_000238877
Letter and report on indoor air quality measurements collected at P.S. 130M to verify acceptable air quality levels.
Similar indexed content
NYC-WTC_000239510
Report from ATC Associates documenting indoor air quality measurements conducted at a school in August 2002.
Similar indexed content