Mr. Bernard P. Orlan April 22, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershin & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and thirty-eight (138) sets of real-time environmental measurements consisting of one hundred and twenty six (126) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 84°F to 88.9°F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature range was 82.4 °F to 88.5 °F.
Relative Humidity
The relative humidity indoors ranged from 36 percent to 45.3 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 36.1 to 45.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 439 ppm to 1050 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentration was 932 ppm. Therefore, the maximum acceptable level of COg at this location was 1632 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NT’AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates fPM2 yt
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 25 pg/m^ with an average 18 pg/m^- All of the indoor measurements for PM2,5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 11 pg/m^ to 52 pg/m3 with an average of 24 ug/m^. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the twelve (12) instantaneous readings were above, USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CONFIDENTIAL, CITY_21MC100_003463998 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260118
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260227
May 2, 2002 IAQ measurements requested by BOE for school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291655
Indoor air quality measurements report for 90 Trinity Place school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259995
IAQ measurements collected Mar 14, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394809
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394752
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370501
Indoor air quality measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238685
Report providing indoor air quality measurements collected at a New York City Department of Education school to verify acceptable air levels.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000238685
Report providing indoor air quality measurements collected at a New York City Department of Education school to verify acceptable air levels.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260227
May 2, 2002 IAQ measurements requested by BOE for school.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
Similar indexed content
NYC-WTC_000260227
May 2, 2002 IAQ measurements requested by BOE for school.
Similar indexed content
NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
Similar indexed content
NYC-WTC_000291655
Indoor air quality measurements report for 90 Trinity Place school, May 2002.
Similar indexed content
April 2002 IAQ measurement summary for the referenced high school.
Similar indexed content