Mr. Bernard P. Orlan May 2, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 REAL-TIME LNMLOXMEM AL MEASUREMENTS

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. B.eadings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 66.5 °F to 77.2 °F. Ninety-eight (98) of the indoor measurements for temperature were below and thirty (30) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor temperature ranged from 58.6 to 73.6 °F.

Relative Humidit\>

The relative humidity indoors ranged from 21.9 percent to 46.8 percent. Sixty-four (64) of the indoor measurements for relative humidity were below and sixty-four (64) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 20.4 to 41.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 442 ppm to 1171 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration w^as 561 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1261 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm These concentrations were below the NP^YAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 19 pg/m^ with an average 5 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour a\'erage concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/nU for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 35 pg/m3 to 138 pg/m^ with an average of 74 pg/m^. Five (5) of the outdoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eleven (11) of the twelve (12) instantaneous outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

CONFIDENTIAL, CITY_21MC100_003464134 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260229

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260229Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399204

IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.

Similar indexed content

NYC-WTC_000259995

IAQ measurements collected Mar 14, 2002 for BOE

Similar indexed content

NYC-WTC_000260159

April 2002 IAQ measurement summary for the referenced high school.

Similar indexed content

Compare copies and versions →