Asbestos air monitoring results, February 2002

Machine-extracted title · confidence 85%

Laboratory report detailing PCM fiber analysis for an ambient air sample collected in February 2002.

NYC-WTC_000235213
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document Sci b#: 202023698 P 1 of 1 Client Name: TRC Environmental Corporation Phase Contrast Microscopy (PCM) Fiber Results 35052-0000-00007; New York City Law Dept.; 100 Church St. Flow Air Fiber Fibers SciLab Client Rate Duration Filtered Density Cone. Fields Fibers TWA Sample # Sample # / Location Collected (Hters/min.) (min.) (liters) (Fibers/mm'^ ) (Fibers/cc)

01 GS-2/25/02/ASB-0683 2/25/02 5 240 1200 100 3 3.82 < 0.002 At Room 6-179 02 GS-2/25/02/ASB-0684 2/25/02 5 240 1200 100 2 2.55 < 0.002 At Room 6-232 03 GS-2/25/02/ASB-0302 2/25/02 5 240 1200 100 3 3.82 < 0.002 At WS-3-160 04 GS-2/25/02/ASB-0303 2/25/02 5 240 1200 100 2 2.55 < 0.002 At WS -3-169 05 GS-2/25/02/ASB-B1 2/25/02 0 0 0 100 0.5 0.64 Blank Footnotes: / 06 GS-2/25/02/ASB-B2 2/25/02 0 0 0 100 0.5 0.64 Blank Footnotes: J Reporting Notes: (1) Fibers/cc cannot be emulated for samples (or blanks) with no air volume. Analyzed by: Fred Corirossi Analyzed; 2/26/02 Samples analyzed by NIOSH 7400(A) Method, Issue ffz, 8715/94: Limit of Detection= 5.5 fibers per 100 fields or 7 fibers/mm2: This report relates ONLY Io the sample analysis expressed as fibers/sq mm of filter area: ND=No fibers observed: NA= Not Analyzed; Walton-Beckctt graticle field area = 0.00785 mm2: TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period not sampled; Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to determine 95% certainty of compliance witli the 0.01 fiber/cc standard; Estimated relative standard deviation: Intralab Sr=0.405, Interlab Sr=0.45, New York samples (NYSDOH ELAP Lab # 11480); National Institute of Standards and Technology Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. AIHA # 102843.

o

S o o o I o to cn Cn

to Ob

NYC-WTC_000235213

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000235213Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →