JLC ENVIRONMENTAL CONSULTANTS, INC.
200 Park Avenue South, Suite 1001, New York, New York 10003
Phone: (212) 420-8119 Fax: (212) 420-6092
Project No.: 01-2102
Metcalf & Eddy Inc; ELAP Lab Code: 11029
Analyte: ASBESTOS
3 Werner Way, Suite 310 NIOSH and AIHA lob Code: 100273 Date Received: 9/28/01
Lebanon, NJ 08833 NVLAP Lab Code: 101953
Date Analyzed: 9/29/01
Batch #: 0109B385
SUMMARY OF ANALYTICAL RESULTS - PLM
Site; 3 World Financial Center - Floors 3-26
S)\MPLE it
ASBESTOS TOTAL % OF rnutiTiri iPNT<t
DATE DESCRIPTION/LOCATION COLOR DETECTED? ASBESTOS CONSTITUENTS
COLLECTED
LAB#
CLIENT'S SAMPLE #
4009 4th Floor/ South East/ Floor/ Sample of GRAY NO 0% CELL 5%
Debris FBGL 20%
9/28/01
NFIB 75%
11055
4-009
•INSUFFICIENT MATERIAL SUBMITTED "TEM RECOMMENDED ***NOT ANALYZED POSITIVE STOP
ASBESTOS CONSTITUENTS NON-ASBESTOS CONSTITUENTS
Sample Analysis by:
Polarized Light Microscopy-Dispersion Staining (PLM-DS) CHRY = Chrysotile Asbestos PAPF = Paper Fiber
AMOS = AmosHe Asbestos MINW ° Mineral Wool
CROC = Crocidolite /Asbestos FBGL = Fiberglass
Method of Sample Preparation and /Xnaivsis: ACTN = Actinolite /tebestos SYNF = Synthetic Fibers
/UI samples were prepared and analyzed in accordance with the EPA TREM = Tremolite /Asbestos • CELL = Cellulose
"Method for the Determination of /Asbestos in Bulk Building Materials' ANTH = Anthophylile Asbestos NFIB = Non-Fibrous
USEPA/ 600/ R-93/116, July 1993. ORGM = Organic Material
WOLL = Wollastonite
Instrumentation: HSHR = Horse Hair
OTHR = Other
Olympus PLM, Model BH-2/VM Stereomicroscope, Model
VMZ 1x-4x. '"Uulam Machhiwala
Laboratory Director
Analytical results reflect the make up of the materials only in the areas sampled. This "Summary of Analytical Results* shall not be reproduced except in full, without the writte.
approval of JLC LaboralOry, and it must not be used by client to claim product endorsement by NVLAP or any agency of the U.S. Government. This method is not applicable to
samples containing large amounts of fine fibers below the resolution of the light microscope. The value of this method is limited to the quantitative identification of asbestos
and the semi-quantitative determination of asbestos content of bulk samples, expressed as a percentage of the protected area. Quantitation of asbestos content was .
determined with a visual volume estimate, a calibrated visual area estimate, and/or point couriting procedure. CAUTION: Other fibers with optical properties similar to asbesto
may give positive interferences and will be considered asbestos under this methodology. Also, PLM is not consistently reliable in detecting asbestos in floor coverings and
similar non-friable organically-bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can b
considered or treated as non-asbestos containing.