Client Name: TRC Environmental Corporation
Phase Contrast Microscopy (PCM) Fiber Results
35052-0000-00004; NYC Law Dept.; 100 Church Street/ Ambient
Flow Air Fiber Fibers
SciLab Client Rate Duration Filtered Density Cone. TWA
Fields Fibers
Sample # Sample # / Location Collected (Jiters/min.) (min.) (liters) (Fibers/mm'^ ) (Fibers/cc)
. 01 GSl 2/2/02 5 120 600 too 30 38.22 0.025
5th Floor Northeast Side
02 GS2 2/2/02 5 120 600 100 21 26.75 0.017
Sth Floor Northwest Side
03 GS3 2/2/02 2.5 270 675 100 4 5.10 < 0.004
Osha Sample On Ceasar Rodriguez
04 GS4 2/2/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 7
05 GS5 2/2/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 7
Reporting Notes:
(1) Fibers/cc cannot be calculated ta (^pUnksixwttffno air volume.
Analyzed by: Tatyana Grimchak_________ Y Date Analyzed; 2/4/02
Samples analyzed by NIOSH 7400(A) Method/lssue???8/15/94: Limit of Detection^ 5.5 fibers per 100 fields or 7 fibers/mm2: This report relates ONLY to the sample analysis expressed as fibers/sq mm of filter area; ND=No fibers observed: NA= Not
Analyzed; Walton-Beckett graticle field area = 0.00785 mm2: TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period not sampled; Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to
determine 95% certainty of compliance with the 0.01 fiber/cc standard: Estimated relative standard deviation; Intraiab Sr=0.405, Interiab Sr=0.45, New York samples (NYSDOH ELAP Lab # 11480); National Institute of Standards and Technology
Accreditation requirements mandate that this report must not be reproduced except in full witliout the approval of the laboratory. AIHA # 102843.
NYC-WTC_000174402
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000174402Source: NYC Law Department, mirrored locally