NYC 9/11 Public Portal Document
OEM Swanke Hayden Connell Architects
7 World Trade Center
Project No.5576A Total RFI's Received 34
Revised 09/03/98 Total Responses Received 29
RFI LOG
HR T GATE- : SUBJECT/DIVISiON/DWG NO. Tr^ponse” ’-iwwe. # BUS Remarks
NO. I REC’D : RESP.
10 7/3198 R.B. SAMUELS NEEDS SIZING OF PIPING AND JUNCTION RESOLVED IN FIELD MEETING ON 8/4/98
BOXES FOR NOVALINK DAT/VTEL/VOICE/RADIO OUTLETS.
THEY HAVE INCLUDED 1" EMT AND SINGLE "J" BOX.
11 7/31/98 CLARIFY FIXTURE TYPE IN ROOM # 23-04 IS IT "E" OR "D-l" ? IT IS TYPE "E" AS NOTED ON DRAWINMGS. 8/498 4
12 8/3/98 MISCELANEOUS ELECTRICAL AND HVAC QUESTIONS ( SEE SEE RESPONSE MEMOM FROM COSENTINI ASSOCIATES 8/4/98 1
ATTACHED LIST) DATED 8/3/98
13 8/6/98 SEE R.B. SAMUELS LETTER DATED 4/8/98 ATTACHED (1) ITEM TO BE ANSWERED BY CA. ALL OTHER ARE TO BE
COORDINATED BY AMBASSADOR CONSTRUCTION.
14 8/6/98 SEE KABACK'S LETTER DATED 8/5/98 ATTACHED SEE ATTACHED FSK'S AND ENGINEERS RESPPONSES.
15 8/6/98 OUR CARPET CONTRACTOR ADVISED US THAT THE C-2 SUBSTITUTE WITH CARPET TILE AS SPECIFIED FOR OPEN 8/5/98 (1)
BROADLOOM CARPET IS NO LONGER AVAILABLE. PLEASE AREAS ON PROJECT.
ADVISE OF SUBSTITUTION.
16 8/6/98 ARE THE FIRE SMOKE DAMPERS PNEUMATIC OR SEE ENGINEERS DESCRIPTION.
ELECTRIC? IF THEY ARE ELECTRIC, WHICH WE THINK THEY
SHOULD BE, WHERE IS THE POWER FOR THEM SHOWN.
17 8/10/98 NEED SWITCH LOCATION FOR LIGHT FIXTURES IN ROOM # LOCATE LIGHT FIXTURE SWITCH AT NORTH AND SOUTH 8/10/98
23-41, 23-39, UNDERCABINET TASK LIGHT IN RM. # 23-21, "D" WALLS OF CORR. NEAR DOOR FOR FIXTURE TYPE "D".
FIXTURE IN CORR. TO 23-43 LOCATE LIGHT SWITCH FOR TASK LIGHTS IN WALL NEAR
DOOR NEXT TO OTHER SWITCHES.
NEED HEIGHT OF GFI RECEPTACLES IN TOILET ROOMS. LOCATE AT 44" A.F.F. TO CENTER LINE OF SWITCH 8/10/98
VERTICALLY.