OEM Swanke Hayden Connell Architects
7 World Trade Center
Project No.5576A Total RFI's Received 34
Revised 09/03/98 Total Responses Received 29
RFI LOG
'RR/-. DATE SUBJECT/DIVISION/DWG NO. RESPONSE BATE #BUS Remarks
NO. REC'D RESP. DAYS
LIGHT FIXTURE TYPE "D" SHOWS 277 V. E2-23 SHOWS 1209 PROVIDE 277V FIXTURE . REVISE CIRCUIT NO. ELC-13 TO
V. PLEASE ADVICE. EHC-13 CONTROLLED BY SWITCH. "SM" REVISE CIRCUIT
NO. ELC-13 & ELC-11 CONTROLLED BY SWITCH "SO" TO
EHB-6. REVISE CIRCUIT NO. ELC-11 TO EBH-6 INWEST
CORR. TO LOCAL SWITCH AS INDICATEDON THE DRAWING.
ELEVATION "A" ON D-1 SHOWS 6 OUTLETSAND ELEVATTION IS CORRECT PLEASE REVISE. 8/10/98
ARCHITECTURAL DRAWING SHOWS 5 PLEASE ADVICE.
NEED HORIZONTAL DIMENSION C-1 AND C-2 OUTLETS IN SEE ATTACHED FSK-5
ROOM 23-21.
OUTLET B-22 IN ROOM 23-51 IS IN PERIMETER COLUMN TO THIS OUTLET WAS TO BE DELETED AS PART OF BULLETIN 8/10/98
BE COVERED BY HURRICANE WALL. PLEASE ADVICE #1
OUTLET AV-17 AND AV-29 ARE NOT SHOWN ON PLEASE ADVISE ON LOCATION OF THESE MISSING 8/10/98
ARCHITECTURAL DWGS. PLEASE ADVICE . OUTLETS.
18 8/10/98 THE PLANS AND SPECIFICATIONS SHOW NO FUTURE VALVE NO VALVE IS REQUIRED FOR FUTURE USE . 8/18/98 REVISED AS PER
AT THE CONDENSER WATER SUPPLY AND RETURN. MR. VAL. LEMESHEV.
SHOULD FUTURE VALVES BE INSTALLED ?
19 8/18/98 DAMPER STATUS PANEL? WHAT IS IT? WHO SHOULD THESE DAMPERS ARE NOT SMOKE CONTROL OR SMOKE 8/20/98 SEE VAL'S
SUPPLY IT? HOW IS IT POWERED? WHERE DOES IT GO? EVACUATION SYSTEM AND DOES NOT REQUIRE STATUS RESPONSE 8/20/98
HOW DO THE DAMPERS OPERATE? INDICATION UNLESS OTHERWISE REQUESTED BY USER.
(please disregard rfi response for rfi # 13.)
20 8/18/98 SHOULD THE HD DAMPERS OUTSIDE THE HURRICANE AS PER LATEST REQUEST FROM USER, BASE PRICE FOR 8/20/98
WALL) IN THE DUCTWORK BE MOTORIZED AND IF SO HOW? "HD" DAMPERS SHAL BE BASED ON MANUAL DAMPERS @
EXTERIOR WALL AND MOTORIZED AT INTERIOR
PROTECTIVE WALL.
21 8/18/98 THE DRAWINGS SHOW THE CONDENSER WATER TO BE PROCEED AS PER PLANS AND SPECIFICATIONS. 8/20/98
TIED INTO A 5" VALVE, THE EXISTING VALVE IS 8". ANY
PROBLEMS?
W \OEM\docs\ RFI LOG 1- xIs Printed 9/8/98 I0 2I AM Pages