7 World Trade Center
Project NO.5576A Total RFI's Received 28
Revised 08/25/98 Total Responses Received 28
RFILOG
RFt DATE SUBJECT/DIVISION/DWG NO. DAIH #BUS Remarks
no. REC’D RESP. DAYS
LIGHT FIXTURE TYPE "D" SHOWS 277 V. E2-23 SHOWS 1209 PROVIDE 277V FIXTURE . REVISE CIRCUIT NO. ELC-13 TO
V. PLEASE ADVICE. EHC-13 CONTROLLED BY SWITCH. "SM" REVISE CIRCUIT
NO. ELC-13 & ELC-11 CONTROLLED BY SWITCH "SO" TO
EHB-6. REVISE CIRCUIT NO. ELC-11 TO EBH-6 INWEST
CORR. TO LOCAL SWITCH AS INDICATEDON THE DRAWING,
ELEVATION "A" ON D-1 SHOWS 6 OUTLETS AND ELEVATTION IS CORRECT PLEASE REVISE. 8/10/98
ARCHITECTURAL DRAWING SHOWS 5 PLEASE ADVICE.
NEED HORIZONTAL DIMENSION C-1 AND C-2 OUTLETS IN SEE ATTACHED FSK-5
ROOM 23-21.
OUTLET B-22 IN ROOM 23-51 IS IN PERIMETER COLUMN TO THIS OUTLET WAS TO BE DELETED AS PART OF BULLETIN 8/10/98
BE COVERED BY HURRICANE WALL. PLEASE ADVICE #1
OUTLET AV-17 AND AV-29 ARE NOT SHOWN ON PLEASE ADVISE ON LOCATION OF THESE MISSING 8/10/98
ARCHITECTURAL DWGS. PLEASE ADVICE . OUTLETS.
18 8/10/98 THE PLANS AND SPECIFICATIONS SHOW NO FUTURE VALVE NO VALVE IS REQUIRED FOR FUTURE USE . 8/T8/98 REVISED AS PER
AT THE CONDENSER WATER SUPPLY AND RETURN. MR. VAL. LEMESHEV.
SHOULD FUTURE VALVES BE INSTALLED ?
19 8/18/98 DAMPER STATUS "PANEL? WHAT IS IT? WHO SHOULD THESE DAMPERS ARE NOT SMOKE CONTROL OR SMOKE 8/20/98 SEEVAL'S
SUPPLY IT? HOW IS IT POWERED? WHERE DOES IT GO? EVACUATION SYSTEM AND DOES NOT REQUIRE STATUS RESPONSE S.'2Q/9S
HOW DO THE DAMPERS OPERATE? INDICATION UNLESS OTHERWISE REQUESTED BY USER.
(please disregard rfi response for rfi # 13.)
20 8/18/98 SHOULD THE HD DAMPERS OUTSIDE THE HURRICANE ■as per latest request from user, base price for 8/20/98
WALL) IN THE DUCTWORK BE MOTORIZED AND IF SO HOW? "HD" DAMPERS SHAL BE BASED ON MANUAL DAMPERS @
EXTERIOR WALL AND MOTORIZED AT INTERIOR
PROTECTIVE WALL.
21 8/18/98 THE DRAWINGS SHOW THE CONDENSER WATER TO BE rPROCEro aTperplans and specification. 8/20/98
TIED INTO A 5" VALVE, THE EXISTING VALVE IS 8". ANY
PROBLEMS?
WAOEM'docsXRFILogVxls Primed 8/25/9S 8:31 AM Pages