ARTICLE 8 GROUNDING CONDUCTORS 3110

Table 1 System Ground Equipment Grounding and Bonding Conductors

Sizei of Largest Circuit Conductor or Equivalent far Multiple Conductors Size of Grounding or Multiple Services Conductor (AWG) Copper Aluminum Copper Aluminum

12 12 16* 12* 10 8 14* 12* 8 6 12* 10* 6 4 10* 8* 4 to 2 0 8 6 1 or 0 2/0 or 3/0 6 4 2/0 or 3/0__ 4/0 or 250 MCM 4 2 Over 3/0 to Over 250 MCM 'T’ 0 350 MCM to 500 MCM Over 3: Over 500 MCM 0 3/0 to 600 MCM to 900 MCM I Over 600 MCM Over 900 MCM 2/0 4/0 to 1100 MCM to 1750 MCM Over 1100 MCM Over 1750 MCM 3/0 250 MCM ' Permissible for equipmeol grounding only but shall not be aniehed M a cireuit COuduclOI. No. 18 copper or No. 14 alutiunum wire shall be minimure uied for portable or pendant equipment grounding if the branch circuit over-current device does not exceed fifteen amperes.

h. The grounded circuit conductor and/or neutral conductor of an interior wiring system shall not be used for grounding conduit, armored cable, other raceways or equipment. i. Lightning rods shall not be used as grounding conductors. j. Grounding conductors of lightning arresters shall not be smaller than No. ( 6 and shall meet the same installation requirements as grounding conductors of interior wiring systems. They shall not be used as system or equipment groun­ ding conductors.

197

SEP-11-iggg 14:30 212 615 3700 97K P.05 NYC-WTC_000172105

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000172105Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.802

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000165112 · Box DEP Box 44

Construction specifications document detailing foundation requirements for the World Trade Center river water intake system relocation project.

Similar indexed content

Compare copies and versions →