b. Manual Paralleling Controls
A selector switch shall be provided to select any generator for manual
paralleling. The switch shall simultaneously connect a phase band
mopitor, synchroscope and manual paralleling pushbutton switch to the
selected generator.
A solid sute Synchronizing Phase band Monitor, Device 25C, shall be
furnished a sync check relay for manual paralleling, pushbutton until the
oncoming generator is within 15 degrees of synchronism.
Operation shall be arranged so that the operator will depress and hold the
manual paralleling pushbutton switch. When the relative phase angle
reduces to 15 degrees and is going toward zero degrees. Device 25C will
initiate the closing of the respective oncoming generator breaker. The
manual paralleling pushbutton switch shall be connected to the selected
generator by the synchroscope selector switch. All controls and metering
for manual paralleling shall be grouped in a central convenient location on
the font of the master control section.
c. DC Control Power Selector - Best Battery System
1) Each generator control unit shall utilize the engine starting
batteries, and a DC-to-DC converter for each engine generator to
provide a 24 Vdc power supply to the generator control PLC
power supply, as backup, during starting and cranking of all
engine generator sets "simultaneously".
2) Control power for the system logic shall be derived from the
engine starting batteries and a separately supplied DC station
battery system. The control logic shall be powered through a
suitable means which shall permit continuity of power until the
last battery is on longer available. The controls shall be powered
from any battery or combination of batteries and prevent
feedback to a failing battery. The transition of control logic
power from any battery combination to any other battery
combination shall be accomplished without disruption in the
power flow. A system logic DC-to-DC converter, shall be
supplied to provide a 24Vdc power supply to the system logic
PLC power supply, as backup, during starting and cranking all
engine generator sets "simultaneously". The DC-to-DC
converter shall not permit the voltage to drop below the 24Vdc
nominal.
OEM PPS-31 Generators
7 WTC March 20, 1998