PRESSURE DROP
AREA FACTOR TABLE
DETERMINING PRESSURE DROP
6.55 4.37 3.28 2.62 2.18 1.87 1.64 1.46 Use the Area Factor Table and
6.65 4.43 3.33 2.66 2.22 1.90 1.66 1.48
3.89 2.60 1.95 1.56 1.30 1.11
g g II JI
Ml M? M? MJ Pressure Drop Chart to determine
II .11 :1? .11 S .11 .11 :S .11 :ll .11 .5?
3.93 2.62 1.96 1.57 1.31 1.12
pressure drop through Ruskin
CD82AF3/CD82AF4 control damp
1:11 Ml Ml g II 5? 11 3 ;ll
1709 79?
1.10
.81 .68
g 1 J? 1 ers.
1. Determine area factor for
II Ml Ml II 11 .11 ;I1 g
.82 .66 :11 .i g g g 1? damper by entering the Area
Ml Ml 1? 769
.69 g :ll II 2 g JI B g g II :ll JI Factor Table through duct
width and height.
Ml g II .51 g g II g g :1^ JI JI JI JI JI g JI 2. Find the conversion velocity
.38
g Ji JI .39 .11 :ll .11 JI JI :ll JI :ll JI g J] J? JI (CV) by multiplying the selected
size damper’s area factor by
.32
g g :ll .32 g 11 g JI JI Ji :ll JI JI J8 g g g II
g ;I1 .27 .27 g g JI JI .JI .JI J? .J? JI .11 S II II II 11
I the flow rate in CFM;
CV = Area Factor x CFM.
3. Enter the Pressure Drop Chart
:ll [I ;ll .24
.24 g JI JI JI JI JI ;ll I :ll 5? :I1 11 II g J at the determined area factor
and proceed up to appropriate
g :ll g .21.19 g JI JI JI Ji JI II s 11 5? g g :ll .11
.21
conversion velocity (CV) line.
Then, read across to static
g g g .17 .19 ;ll JI JI JI -.11 Jl g S :ll II II II
JI JI
aa
:11 g .17
g .15
:tl JI JI :g :ll 11 11 1 :ll II II II 11
.16 JI J] JI g g .:ll .H 51 :ll .11 .11 :g 11
pressure drop at left side of
chart.
;ll JI .14 JI JI g 11 IT g K S' II 11 11 11 11
.14
.13 JI II g g 1 II g 11 .11 g
:ll g JI .13 11 11 II II
g -.11 JI .11.12 :t5 11 •.n g II g [i 11 g 11 II II II
.12 &
g g JI .12 g :ll 11 g g II :ll 11 11 11 5: II II :ll II
Example:
Find the pressure drop across an 18" wide x 18" high Model CD80AF4 control damper handling 8570 CFM. From the Area Factor Table, area factor
is determined to be .58.
CFM X AREA FACTOR EQUALS CONVERSION VELOCITY
Therefore, CV (Conversion Velocity) = 8570 CFM x .58 = 5000. Using the pressure Drop Chart, pressure drop = .20 inches water gage.
CD80AF PRESSURE DROP CHART
10
.90
.SO
70
.80
.50
<0
o .40
o .30
IM
.20 •
O
x:
o
.10
lU .09
.08
fiC .07
3 06
W
w 06
UJ 04
fiC
Q.
03
2
»- 02
«
01 .02 04 05 06 06 3 4 5 6 20 30 8 10
07 09 7 9
NOTE: AREA FACTOR
1. Ratings are based on AMCA Standard 500 using Test Setup Apparatus Figure 5.3 (damper is installed with duct upstream and down
stream).
2. Static Pressure and Conversion Velocities are corrected to .075 Ib./cu. ft. air density.
NYC-WTC_000166825