5.2 Draft Progressive Collapse Guidelines t
5.2.1 Guidelines
(a) General Considerations
Progressive collapse is the propagation of collapse to an extent disproportionate to the initiating zone of
damage and is interpreted as structural failure beyond the point of initial damage extending vertically over
more than three stories and horizontally over an area greater than one structural bay or 20 percent of the
horizontal area of the building, whichever is less. ASCE 7-98*'’ cites three design alternatives for providing
structural resistance to progressive collapse, including the indirect design approach, the direct design
alternate path and the direct design method of specific local resistance. The indirect approach is a
f
I
prescriptive consideration of resistance to progressive collapse through the provision of minimum levels of
strength, continuity and ductility. The direct design alternate path method allows local failure to occur but
provides alternate load paths to bridge over the damage and avert collapse; The direct design method of
specific local resistance provides sufficient strength to resist failure. If the design cannot accommodate the
prescriptive design and detailing requirements of the indirect method, the alternate path approach can be
used to quantify the extent ofductile detailing required for new construction. Where neither the indirect nor
the alternate path approaches can be accommodated or where project specific threats are identified, the
individual members can be locally hardened and detailed to develop the full resistance of each key element
against unanticipated load without failing the connections or supporting members framing it. When the
building contains materials that pose a high risk including high fiiel loads, combustible/flammable liquids
explosive materials, toxic gases, etc. the effects of fire must be considered by separate analysis. This
balanced approach develops the full resistance available to the key members and provides comprehensive
resistance to progressive collapse. The load path of the structure should be taken in consideration in
determining the appropriate method of evaluation.
Where the Direct Design Alternate Path Method, or the Direct Design Specific Local Resistance method
are utilized, licensed professional engineer(s) should demonstrate by analysis that the design is resistant to
progressive collapse when exposed to credible threats including fire. To protect against a reduction in
capacity and differential thermal expansion that may result in progressive collapse from extended exposure
to fire, the structural members and components should be designed and have a fire resistance rating
appropriate to their designed function. These structural members and components should be appropriate for
associated hazards/threats and credible fire loads, the predicted fire intensity and duration of these fire
loads, the height and the use/occupancy of the specific building or space, established goals, objectives, and
level of risk acceptable to the stakeholders, fire and life safety features provided, and proximity to adjacent I
structures and properties so as to limit the potential for progressive collapse. !
Transfer structures should be continuous over several supports with substantial structure framing into these
members to create a two-way redundancy that provides an alternate load path in the event of a localized
failure. The column connections, which support the transfer structures, should provide sustained strength
despite inelastic deformations and designed as full moment connections. Transfer structures and the
columns that support the transfer members should be hardened to the requirements of the specific local
resistance. These guidelines also apply to transfer systems and to all elements that have no redundancy,
such as tension hangers and tension ties in trusses. These elements should have connections that develop
the full axial strength of the member (AgFy). All elements of a transfer system will be designed for the
lowest strength reduction factor used in the design of any supported, supporting or transfer element. The
transfer system and non-redundant key members are to be designed to sustain extended exposure to fire
corresponding to the bum out of the floor on which it is located.
(b) Definitions
Kev Members are defined as those structural elements at any one story whose loss results in a collapse of
the structure more than one story above or below the element under consideration, or over a horizontal area
in excess of that stipulated in the criterion. These critical load-bearing members correspond to: j
(1) Any single “wall panel or nominal length thereof.” i MW
' American Society of Civil Engineers Minimum Design Loads for Buildiiigs and Other Structures,
Revision of ANSI/ASCE 7-98, Section Cl.4 General Structural Integrity
Page 30 WTC Building Code Task Force February 2003
Findings and Recommendations