5 Appendix
5.1 Rules of the City of New York: Resistance To Progressive Collapse
Under Extreme Local Loads (Current Provisions)
From: NYC Building Code - Appendix A: Selected Rules of the Department of Buildings
CHAPTER 18 RESISTANCE TO PROGRESSIVE COLLAPSE UNDER
EXTREME LOCAL LOADS
§18-01 Considerations and Evaluation.
(a) General considerations. Unless all members are structurally connected by joints capable of
transferring 100% of the members' working capacity in tension, shear, or compression, as appropriate,
without reliance on friction due to gravity loads, the layout and configuration of a building and the I
interaction between, or strength of, its members shall provide adequate protection against progressive
collapse under abnormal load, where progressive collapse is interpreted as structural failure extending
vertically over more than three stories, and horizontally over an area more than 1,000 square feet or 20
percent of the horizontal area of the building, whichever is less. These criteria shall be satisfied while
the building is subjected to its own weight D plus a superimposed load [resulting in an equation] of
(l.OD-I-0.25L), where D is computed according to Article 2 of Subchapter 9 of Chapter 1 ofTitle27 ।
of the Administrative Code and according to Reference Standard RS 9-1 of the same Code and L is
computed according to Article 3 of Subchapter 9 of Chapter 1 of Title 27 of the Administrative Code
and according to Reference Standard RS 9-2 of the same Code without allowance for the live load
reduction permitted in Article 4 of Subchapter 9 of Chapter 1 of Title 27 of the same Code. A wind )
load of 0.2 W shall be assumed to act in combination with l.OD ■+• 0.25L, where W is computed I
according to Article 5 of Subchapter 9 of Chapter 1 of Title 27 of the Administrative Code and
according to Reference Standard RS 9-5 of the same Code. These criteria shall be satisfied in
accordance with structural analysis based on the Plastic Design or Ultimate Strength method,
representing conditions at incipient failure and shall be considered as an independent check of a
building designed in accordance with the usual procedures for Working Stress, Plastic Design, or
Ultimate Strength design pursuant to Subchapters 9, 10, and 11 of Chapter 1 of Title 27 of the
Administrative Code and all applicable Reference Standards thereto.
(b) Methods of evaluation.
Resistance to progressive collapse shall be determined by one of two methods:
(1) The Alternate Path Method.
(2) The Specific Local Resistance Method.
The specific local resistance method shall only be used if the alternate path method is not feasible.
(i) The Alternate Path Method.
Proof shall be provided, by analysis and/or physical simulation, that the following condition is satisfied
while the building is subjected to the loads stipulated in the criteria:
(A) Should any one of the following combinations of structural elements at any one story lose its
ability to carry load, there shall be no collapse of the structure more than one story above or below the
element under consideration, or over a horizontal area in excess of that stipulated in the criterion:
(a) Any single "wall panel or nominal length thereof."
(b) Two adjacent "wall panels or nominal lengths thereof forming an exterior corner to the building.
(c) One or more elements forming a "nominal extent of flooring".
(d) One column.
fej Any other one element of the structural subsystem which is judged to be vital to the building's
stability.
(B) The following definitions specifically apply to Method (b)(1):
(a) The designation "wall panel or nominal length thereof is the smaller of the following lengths as
i
appropriate to the design in question;
(I) The length between adjacent lateral supports.
(2) The length between a free edge and the nearest lateral support.
(3j A length equal to 2.25 times the clear height of the wall panel in those circumstances where the top
and bottom attachment of the panel to the floor or roof will not fail under a force smaller than 3 kip per 11
linear foot acting perpendicular to the wall in either direction.
(b) As used above, "lateral support" is considered to occur at:
(}) A substantial partition perpendicular to the wall, provided that its attachments to the wall and the
partition itself are capable of resisting and transmitting without failure a horizontal force of 3 kip
Page 28 WTC Building Code Task Force February 2003
Findings and Recommendations
/
NYC-WTC_000166514