Air Monitoring Requirements
8®ai?5' For
125 Cedar Street
Equipment
Sampling equipment must be in sufficient quantity to provide the amount and type of samples
required for this project. At a minimum the following equipment are required: air-sampling pumps
with flow rate capacities of 2 to 10 liters per minute, tripods, rotometers, sample cassettes with
mixed cellulose ester filters having pore size of 0.45pm(TEM).
Specificatiops
It is anticipated that the work will be completed within three (3) weeks.
Air Sampling Analysis
All air samples shall be analyzed via TEM. The method of analysis and sampling methodologies shall
be governed by New York City Department of Environmental Protection (NYCDEP) Title 15 and New
York State Industrial Code Rule 56 (NYSICR 56). A turnaround time of 24 hours is required for all
samples.
Air Monitoring
1. A minimum of five (5) samples per day is required during cleanup activities.
2. Samples shall be collected at isolation barriers outside the work area, the clean room of the
worker/waste decontamination facility, and outside of the building.
3. Sample collection shall be in accordance with Title 15, Chapter 1 of the Rules of the City of New
York (RCNY) and New York State Industrial Code Rule 56 regarding sample locations, rate of flow,
and required volumes to achieve the necessary analytical sensitivity.
4. Sampling equipment shall be placed at representative locations and away from obstruction.
Sampling cassette must be placed on a tripod and not taped to existing surfaces. All air sampling
equipment shall be pre- and post- calibrated to insure accurate air sampling volumes.
5. The Air Sampling Technician shall perform clearance air sampling in accordance with Title 15,
Chapter 1 of the RCNY after the areas are free of dust accumulations as determined by the Project
Monitor. All surfaces must be completely dry prior to the start of sampling. Clearance air sampling
shall be performed at each unit. A minimum 10 samples shall be collected on each floor. The
elevator shaft and first floor commercial spaces shall be cleared separately. Clearance air
monitoring shall be performed after the completion of all clean up activities at the work site.
6. The apartment will be re-cleaned and retested if the clean-up criterion of 70 structures/square
millimeter (70 s/mm^ measured by TEM) is not achieved. This clean-up criterion may be
reevaluated and revised, if determined necessary based on field conditions and analytical limitations.