December 17, 2002 114 LIBERTY STREET
REMOVAL OF DUST, DEBRIS, AND CONTAMINATED MATERIALS
11 DECONTAMINATION UNITS
PART 1 - GENERAL
1.01 RELATED DOCUMENTS:
A. Refer to Section 06 Temporary Facilities for electrical requirements and requirements relative to
connection of decontamination facilities to building systems such as water, sewer, and electrical.
1.02 DESCRIPTION OF WORK:
A. Provide Personnel and Equipment Decontamination facilities. Require that the Personnel
Decontamination Units be the only means of ingress and egress for the Work Area. Require
that all materials exit the Work Area through the Equipment Decontamination Units.
PART 2 - PRODUCTS
2.01 MATERIALS AND EQUIPMENT:
A. Provide new or used materials and equipment that are undamaged and in serviceable condition.
Provide only materials and equipment that are recognized as being suitable for the intended
use, by compliance with appropriate standards.
B. Framing Materials and Doors: As required to construct temporary decontamination facilities and
critical barriers. Lumber shall be high grade, nevy finished on side, and fire retardant.
C. Fire Retardant Clear Polyethylene sheeting that conforms to requirements set forth by the
National Fire Protection Association Standard 701, Small Scale Fire Test for Flame-resistant
Textiles and Films. Minimum thickness 6 mil; provide largest size possible to minimize seams.
D. Fire Retardant Black Plastic Sheeting, minimum thickness 6 mil: as required to obstruct view of
abatement activities: provide largest size possible to minimize seams.
E. Tape: Provide tape which is of high quality with an adhesive which is formulated to aggressively
stick to sheet polyethylene, as manufactured by Kendall Co., NASHUA Tape Products; or
approved equal.
F. Spray Adhesive; Provide spray adhesive in aerosol cans which is specifically formulated to stick
tenaciously to sheet polyeth^ene, as manufactured by 3M; NASHUA Tape Products; or
approved or equivalent.
G. Shower Pan: Provide one piece stainless steel shower pan with a minimum 6" depth.
H. Shower Head and Controls; Provide a factory-made showerhead producing a spray of water
that can be adjusted for spray size and intensity. Feed shower with water mixed from hot and
cold supply lines. Arrange so that control ofwater temperature, flow rate, and shut off is from
inside the shower.
45
© AMBIENT GROUP, INC. - 2002
DECONTAMINATION UNITS
NYC-WTC_000155762