Draft2 Comments by Covino Environmental Associates, Inc. January 6.2003

Use isolation/zone pillows as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone and to prevent cross-contamination of cleaned sections by work in sections not vet cleaned.

-7.06eupied areas or common areas in -which-fan unit cleaning is accomplished, will be cleaned as common spaces using the-eemmon space unit prices, immediately after the HVAC oleamng is-complete.

S.These areas identified in 6 above will-be air tested immediately after cleaning of the eommen space and analysis will be accomplished on a RUSH basis.-These-areas should not be opened for re oocupancy-until successfal results aren-eceived.

9. A local c-apture, HEPA filtered, Air Filtration Device (AFD) will be attached to the lowest opening of a riser or the furthest point of a horizontal duct, to place the system under negative pressure.

lO.Insert and inflate 4solation/zone- pillows, as necessary 40 isolate system, so that the cleaning does not extend outside the work zone.

11 .Remove-and clean all grills along the affected ductwork.

12.Clean all branch ducts using HEPA vacuums with-brush attachments and wet methods.

13. Apply encapsulant to any exposed porous insulation in the AC/ventilation system fan unit or ducts.

14. Protect the floor underneath the supply grilles/diffiisers or return air grilles using 6 mil polyethylene sheeting. Remove the polyethylene barriers covering the supply air diffusers/grilles and return grilles, while the duct is still under negative pressure.

13.Reinstall grills and install-one layer of 6 mil poly-over grills and secure in place with painters tape.

15. Remove supply air grilles and diffusers to a central location for cleaning. Clean using Simple Green or a similar environmentally safe product. Use bags if necessary when removing the grilles and/or diffusers to prevent dust or debris from being released. Reinstall supply grilles/diffitsers and return air grilles after cleaning.

IdTClean-die main duct starting from the furthest point away from the local of^ture-AFD? (usually at the fan unit)r-using-a combination of techniques including whips, brushes, and compressed-air xmtil no suspect WTC dust is apparent.

15.Remove- the-poly barriers, covering the exhaust gills, while the duct-is still under negative pressure se-that-any loose dust or debris will be sucked into the capture system.

16. Remove and replace air filters within the AC/ventilation system fan unit or ducts.

NYC-WTC_000140015

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000140015Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →