were collected of dust/debris from various locations. A total of twenty-three (23)
dust samples were collected.
All samples collected were transported to an independent certified laboratory,
EMSL Analytical, for analysis. Samples were analyzed utilizing Polarized Light
Microscopy (PLM) Methodology via the NY State ELAP 198.1 method. Dust
Samples were tested negative for presence of asbestos. Please see Section V for
locations and results.
All surfaces affected such as but not limited to the air-handling units, passenger/ freight
elevators, main lobby, secondary lobbies, staircases and affected suites were wet wiped
and HEPA vacuumed by a licensed asbestos contractor. All air filters within the said fan
0 units wore removed and disposed of as asbestos waste.
In addition to the above, CTS! performed ]Dust Particulate testing from various areas of
the building. Dust Particulates were collected utilizing a Nephelometric Laser Scatter
Total Dust Measure method. This method utilizes the diffraction of laser beams
to
evaluate the density of dust in the beam path. It is sensitive to as little as one tenth of one
microgram of dust per cubic meter of air (0.1 UG/M3). The test results were acceptable
and within the established OSHA standards. Please see Section VII for locations and
results.
X)ue to the outside air conditions with elevated dust levels and fumes from the World Trade
Center clean up process, Ci'SI recommends that the outside fresh air louvers be kept closed
and only opened when outside air has bees checked by building engineering staff to be odor
and dust free. Lack of fresh outside air will result in elevated Carbon Dioxide levels during
building full occupancy after 10:00 AM. Tenants may report an increase in
symptoms such
as but not limited to headaches, mild dizziness and fatigue.