Ambient Air Sampling
ASSOCIATES INC.
Fib In Air via PCM
analyzed for
Twelve ambient air samples collected within the common areas lobby were
method. All samples collected
fiberglass using the Phase Contrast Microscopy (PCM) analytical
recorded fiber levels less than 0.01 f/cc
In the absence of a specific ambient air standard for fiberglass, ATC has selected as a criteria
following an
for acceptable ambient air sample sets, the NYCDEP re-occupancy requirement (o.ol
0,01 fibers per cubic centimeter
asbestos abatement action of an average of less than
f/cc2).
concentrations
In conclusion, based upon the analytical results for fiberglass recording fiber action, it is
below the NYC acceptable airborne clearance requirement following an abatement
ATC's opinion that the ambient air samples collected throughout the building meet an
acceptable criterion for re-occupancy
PCB's in Air
analytical
One ambient air sample collected within the lobby and analyzed for PCB's recorded
results less than analytical detection limit.
Indoor Air Quality
The IAO evaluation included collection of seventy-five real-time measurements of temperature,
relative humidity, carbon dioxide (CO2), carbon monoxide (CO), respirable particulates and total
volatile organic compounds (TVOC). Currently, there are no regulatory standards for indoor air
quality in non-industrial buildings, such as residential units. For the real-time data collected,
ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999). American Society of
Heating. Refrigerating, and Air-Conditioning Engineers (ASHRAE):
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
PARAMETER TARGET LEVEL AGENCY OR
ORGANIZATION
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
CO above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
CO ASHRAE 62)
Respirable Particles 50 micrograms per cubic USEPA NPAAQS (as cited in
(PM10) meter of air /m3 ASHRAE 62)
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter. 68-75°F at 50% RH
Relative Humidity 30-60 % ASHRAE 55