I SCOPE OF WORK
1. All grilles and diffusers, either internal to apartments or in common areas, will be treated as
' follows:
a. The grille will be removed and bagged.
' b. Each grille will be water and detergent washed.
c. Each grille will be sanitized with an anti-microbial agent.
d. The grille will be re-installed.
the cleaning.
e. Access to each apartment will be required three (3) times on the day of
1. The grille will be removed and the ductwork will be sealed.
2. The horizontal ductwork will be cleaned.
P 3. The grille will be re-installed and housekeeping will be done.
2. The kitchen and exhaust ductwork will be addressed as follows:
a. The horizontal ductwork will be cleaned using a pneumatic-powered whip.
b. The horizontal ductwork will be HEPA vacuumed.
brush depending on
C. The vertical risers will be cleaned with a pneumatic whip or rotating
the internal size.
'
d. Any debris will be trapped in a HEPA-filtered collection device.
' e. The exhaust fans will be disassembled, HEPA-vacuumed and re-assembled.
be treated
f. All internal surfaces, from terminal ends of horizontal to the rooftop fan, will
sprayer or by a hand-wiping method (from the
with an anti-microbial agent via an airless
rooftop to the bottom of the vertical run).
3. The air-handling systems and associated ductwork will be addressed as follows:
a. The HVAC system will be sequentially addressed in the direction of the airflow.
b. The return ductwork grilles will be cleaned as discussed in Section 1.
C. The horizontal ductwork will be cleaned using pneumatic whip.
a
I d. Any debris will be collected in a HEPA-filtered collection unit.
a
e. If internal cross-section of the ductwork is larger than 24 inches by 24 inches,
technician will enter it and will contact-clean with a HEPA vacuum.
f. The outside air intake louvers will be pressure-washed or HEPA-vacuumed, as
applicable.
g. All internal surfaces of the air-handling unit will be HEPA vacuumed to 99.97%
efficiency at .3 microns.
h. The coils will be high-pressure water-washed or HEPA vacuumed, as applicable.
i. The supply ductwork will be cleaned using the same protocols described above.
All internal surfaces of the air delivery system will be treated with an anti-microbial
I j.
agent via an airless sprayer or hand-wiping method.