Tribeca Park — 400 Chambers Street ATC Project No.: 09622-0012 Related Management Company, L.P. February 15, 2002 Page 5

Based upon analytical sample results for all samples recording levels below the AHERA clearance requirement, it is ATC's opinion that the ambient air samples collected throughout the building are representative of the ambient conditions at the time of testing and that the areas tested meet an acceptable criterion for re-occupancy.

Fiberglass in Air via PCM Twelve ambient air samples collected within the common areas lobby were analyzed for fiberglass using the Phase Contrast Microscopy (PCM) analytical method. All samples collected recorded fiber levels less than 0.01 f/cc In the absence of a specific ambient air standard for fiberglass, ATC has selected as a criteria for acceptable ambient air sample sets, the NYCDEP re-occupancy requirement following an asbestos abatement action of, an average of less than 0.01 fibers per cubic centimeter (0.01 f/cc2). In conclusion, based upon the analytical results for fiberglass recording fiber concentrations below the NYC acceptable airborne clearance requirement following an abatement action, it is ATC's opinion that the ambient air samples collected throughout the building meet an acceptable criterion for re-occupancy

PCB's in Air One ambient air sample collected within the lobby and analyzed for PCB's recorded analytical results less than analytical detection limit.

Indoor Air Quality The IAQ evaluation included collection of seventy-five real-time measurements of temperature, relative humidity, carbon dioxide (COZ), carbon monoxide (CO), respirable particulates and total volatile organic compounds (TVOC). Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as residential units. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications: • Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); • Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); • Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

NYC-WTC 000102773

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000102773Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →