The 41 µg/ft2 sample was taken from glass table top in Room 527. The room
a
window was left open during the disaster and the floor and room contents are
covered with dust. The 69 µg/ ft2 sample was taken from the vinyl flooring in
the southwest corner of the second floor.Again, windows were left open and
the floor and office contents are covered with dust. This testing indicates that
significant lead contamination is not a problem in the building. The affected
areas require some cleaning, which is discussed later in this report.
Asbestos Air Samnlin
10 air samples (one per floor) were taken and analyzed by an accredited
asbestos laboratory using transmission electron microscopy (TEM) TEM
analysis is accurate for finding even trace amounts of asbestos fibers
very
present in the air.
The United States Environmental Protection Agency (EPA) has established a
protocol for determining whether school areas are safe for re-occupancy after
completion of asbestos abatement projects. This procedure is covered by EPA
40 CFR Part 763, Asbestos-Containing Materials in Schools. The procedures
state that the average asbestos airborne fiber level in the abated work area
must be less than 70 asbestos structures per square millimeter (AS/mm2).
The laboratory results from the testing on September 25, found no asbestos
structures present in 8 of the samples. 2 samples had one asbestos structure
(fiber) present and the levels were well below the allowable 70 AS/mm2.
Reference the attached laboratory results from EMSL Analytical.
Very low levels of asbestos exist in the New York City urban environment. Two
samples with one asbestos structure present in a total sampling of 10 is
considered statistically insignificant.
HVAC Asbestos Sampling
The air handling units have not operated since the morning of September 11,
2001. Dust samples were taken in the immediate vicinity of the air handling
unit outdoor air intakes on each floor. A total of 23 samples were analyzed by
the accredited asbestos laboratory using polarized light microscopy (PLM).