Re: Environmental Testing Page 4 of 5
Five samples were identified as asbestos containing materials (ACM). An ACM
is defined as a material with greater than one percent asbestos. 14 samples
were found to have trace (i.e., less than 1%) asbestos content. Levels less than
one percent are not regulated. Four samples had no asbestos detected. The
laboratory results demonstrate that asbestos contamination is present at or
near every outdoor air intake in the building. Reference the attached laboratory
results from EMSL Analytical for locations.
The air handling unit (AHU) air cooled condenser coils and ducts are heavily
contaminated with dust. This portion of this system does not handle any
ventilation air that is distributed to occupied areas within the building.
With the AHUs not in operation, the outdoor air dampers were closed at the
time of inspection. The damper seal appears normal, however some opportunity
for leakage was observed. The mixed air plenums and unit interiors have
minimal visible dust. The distribution ductwork was not inspected on
September 25, 2001.
Based on the asbestos levels detected and visual inspection, all air handling
units in the building require a thorough cleaning. As a precaution, all air
distribution ducts and the mechanical equipment rooms should also be
cleaned. The firm and personnel performing the cleaning should be certified as
an HVAC Duct Cleaning Specialists (e.g., National Air Duct Cleaners
Association). The firm must also have experience and certifications for asbestos
abatement. Independent asbestos and dust testing should be performed by an
Environmental Consultant after project completion and prior to occupancy.
Asbestos Surface Sampling
Asbestos settled dust sampling was performed in at least two locations (north
and south) on each floor of the building (except the Penthouse (no access) and
Basement). A total of 21 samples were analyzed by the accredited asbestos
laboratory using polarized light microscopy (PLM).
20 samples had no asbestos detected. One sample had trace (i.e., less than
1%) asbestos content. The trace sample was taken from the carpet in Room
527. The room window was left open during the disaster and the floor and
room contents are covered with dust.