Temperature 26° F 29° F
Relative humidity 17.0% 24.0%
Carbon dioxide 301ppm 335ppm
Carbon monoxide 0 0
ASHRAE recommended Comfort Guidelines:
Relative Humidity Winter Temp (°F) Summer Temp (°F)
30% 68.5-76.0 74.0-80.0
40% 68.5-75.5 73.5-79.5
50% 68.5-74.5 73.0-79.0
60% 68.0-74.0 72.5-78.0
CO2= 1,000 ppm (upper limit)
OSHA Permissible Exposure Levels (ppm)
Carbon monoxide (CO) 35 ppm
Metliods of Monitoring:
Temperature and were measured using a Cole Palmer Thermo
Relative Humidity (RH) hygrometer TH-100.
Carbon Dioxide (CO2) Monitoring for CO2 was conducted with a Testo535 portable
measuring instrument.
Carbon Monoxide (CO) Monitoring for CO was performed with a Gas Tech Meter Model-
GX-91.
Flow rate Monitoring flow rate was conducted with TSI
Model 8357 Velocity Meter.