Indoor air quality report, Stuyvesant High School, Jan 2002

Machine-extracted title · confidence 41%

ATC report of IAQ measurements at Stuyvesant High School.

NYC-WTC_000311232–000311235
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Temperature

Indoor dry bulb temperature measurements ranged from 69.5 °F to 77.2 °F. Twenty-three (23) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from pt, 4th, 5th and bt'"' floors. The outdoor temperature range was 53.0 to 53.5 °F.

Re/ative Humidity

The relative humidity indoors ranged from 23.9 percent to 45.0 percent. Five (5) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other relative humidity measurements were below the ASHRAE-recommended range. The outdoor relative humidity range was 37.1 and 37.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 522 ppm to 3200 ppm. Twelve (12) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 400 ppm and 455 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1155 ppm (background level ■+• 700 ppm). The highest reading, 3200 ppm, was in Room 125. Room 125 had approximately 150 people at the time ATC’s collected the CO2 measurement. Rooms with CO2 levels above the recommended maximum were found on pt, 411'', 5th, gtly 7th, gth, 9th and lOl'i floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates CPM2,5}

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 38 pg/m^. All measurements were below the NPA.AQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 38 and 49 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

CITY_21MC100_003044934

NYC-WTC_000311234

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311234Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000274045

December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

Compare copies and versions →