Temperature
Indoor dry bulb temperature measurements ranged from 69.5 °F to 77.2 °F. Twenty-three (23) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from l^t, 4th, 5*:^ and 6^^ floors. The outdoor temperature range was 53.0 to 53.5 °F.
Relative Humidity
The relative humidity indoors ranged from 23.9 percent to 45.0 percent. Five (5) measurements . were within the ASHRAE-recommeiided range of 30 to 60 percent for occupant comfort. All other relative humidity measurements were below the ASHRAE-recommended range. The outdoor relative humidity range was 37.1 and 37.6 percent.
Carbon Dioxide Concentratipn
Carbon dioxide concentrations indoors ranged from 522 ppm to 3200 ppm. Twelve (12) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 ■- concentrations were 400 ppm and 455 pprn. Therefore, the maximum acceptable level of CO2 at ■ this location was 1155 ppm (background level + 700 ppm). The highest reading, 3200 ppm, was - SSIS in Room 125. Room 125 had approximately 150 people at the time ATC’s collected the Cp2 ■ measurement. Rooms with CO2 levels above the recommended maximum were found on 1^^, 41'1, 5*^'^, 6th-, 7th, gth, 9th and 10th floors. Levels above the recommended maximum do not '•/’ indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 38 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hoiir average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 38 and 49 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentration
TVOCs were not detected anywhere inside, the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
'll C11X_21MC100_00289m0
NYC-WTC_000401775
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000255807
ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311232
ATC report of IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311250
ATC report of IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401743
Indoor air quality measurements report for Stuyvesant High School, January 8, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255777
ATC memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311194
ATC report of indoor air quality measurements at Stuyvesant High School (M477).
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401790
ATC reports IAQ measurements taken January 11, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401819
ATC indoor air quality report dated January 16, 2002 for Stuyvesant High.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311190
ATC report on indoor air quality measurements at Stuyvesant High School (M477).
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274045
December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401524
Indoor air quality measurements conducted December 17–18, 2001 at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311269
ATC report of IAQ measurements collected at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000255807
ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 2002.
Similar indexed content
ATC report of IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000311250
ATC report of IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000401743
Indoor air quality measurements report for Stuyvesant High School, January 8, 2002.
Similar indexed content
NYC-WTC_000255777
ATC memo detailing IAQ measurements at Stuyvesant High School.
Similar indexed content