Part V - Quality Assurance Project Plan
133-135 Greenwich Slreet/21-23 Thames Street
Airtek Project 05-0701 - November 4, 2005
Duplicates^ when positive laboratory Overall
results for both precision; and
samples are > /or qualify
5x QL data.
*No situation
where one
result is
detected at >
5x QL and
other result is
not detected
Laboratory 1/prep batch Percent Determine Accuracy/Bias
Control recoveries 80- cause of
Sample 120% problem,
reanalyze,
and/or qualify
data.
Method Blanks 1/prep batch Mercury must Reclean, Accuracy/Bias-
be < 15 ng per reanalyze Contamination
trap and/or qualify
data
Calibration 1/10 samples Mercury must Reclean, Accuracy/Bias-
Blanks be < 50 pg reanalyze Contamination
and/or qualify
data
Field Spikes 4 Percent Reanalyze Accuracy/Bias
spikes/background recoveries 80- and/or qualify and Precision
phase followed by 120%; % RSD
1 spike/every other < 30 in
week background
phase
Duplicate Every sample, RPDs must be Reanalyze Precision
Injections blank, QC <10 when and/or qualify
positive results
for both
injections are
> 5xQL
Triplicate Every 10 samples %RSD< 10 Reanalyze Precision
Injections when positive and/or qualify
results for all
injections are
45