Part V - Quality Assurance Project Plan
133-135 Greenwich Slreet/21-23 Thames Street
Airtek Project 05-0701 - November 4, 2005
Field/Trip 1/day 0±3 gg Qualify Accuracy/Bias-
Blanks data Contamination
Data NA Field 90%; NA Data
Completeness Laboratory Completeness
Check 95%
Sample 1/10 ± 10 pg Qualify Precision
Reweigh samples data
gross
weighing
1/10 ± 10 gg Qualify Precision
samples data
gross
weighing
' Will be collected at a frequency of 1/day; during Abatement and Demolition
Phases only 1 field/trip blank per week will be analyzed.
TABLE 8.10
Measurement Performance Criteria
Waste Sample Analysis - VOC, SVOC, Pesticides/Herbicides/PCB, Metals/Mercury, pH
Instrument Activity Frequency Acceptance Corrective SOP
Criteria Action Ref.*
Retune GCMSVOC011700
BFB Tuning Every 12 Method 8260B Criteria
GC/MS hours As Recalibrate system Revision 1.7
Initial cal. (5 CCC RSDs < 30%’ Rf for
Volatiles stds) Method needed SPCCs >0.05, RSD Avg < Rerrm blank, rerun
blank Every 12 15% affected samples
hours Acetone, MeCL < 25 ppb Rerrm cal chk and
Cont.
calibration Every 12 CCCs < 25%D; SPCCs > all affected samples
hours 0.05 Rerun affteced
Surrogate stds.
All Within Laboratory Control samples
Laboratory
Control Once/20 limits Renrn LCS and all
samples affected samples
MS/MSD
Once/20 -50% to+100% of 12 hr Rerun MS/MSD and
Internal
samples Cal. affected samples
Standards
ALL Rerun affected
samples
Recalibrate System GCPESTO11799
Initial cal. (5 As needed RSDs all <20%
GC Pesticides/ stds) Cont. Rerun all affected Revision 1.1
Every 10 < 15 % Difference
Herbicides and calibration samples under good GCHERBO11999
samples
PCBs (midpoint)
Not detected cev
one per Revision 1.2
method blank Within Lab control limits Reextract, rerun
batch GCPCBO11799
surrogate stds. Within lab control limits Re extract samples
All Revision 1.2
MS/MSD & with both surrogates
Once per out
LCS
20 samples
Reextract or
reanalyze affected
samples where LCS
is out.
49
CITY_21MC100_003237453
NYC-WTC_000447482
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000447482Source: NYC Law Department, mirrored locally