NYC 9/11 Public Portal Document
Part V - Quality Assurance Project Plan
133-135 Greenwich Street/21-23 Thames Street
Airtek Project 05-0701 - Rev 1 - February 1, 2006
Data NA Field 80%; NA Data
Completeness Laboratory Completeness
Check 95%
Tab/e 8-5. Measurement Performance Criteria Tab/e-PCDDs/PCDFs HRGC/HRMS
QC Sample or Frequency Measurement Corrective DQI
Activity Performance Action
Criteria
Field 1/Week *RPD < 40 Assess Precision-
Duplicates when positive laboratory Overall
results for both precision; and
samples are > /or qualify data.
5x QL
*No situation
where one
result is
detected at > 5x
QL and other
result is not
detected
Extraction Every sample, Percent Reanalyze Accuracy/Bias
Standards (pre blank, QC recoveries 50- and/or qualify
extraction) 120% for tetra data.
hexa congeners
and 40-120%
for hepta and
octa congeners
Field Spikes Every sample, Percent Reanalyze Accuracy/Bias
(pre-sampling) blank, QC recoveries 70- and/or qualify
130% for data.
Laboratory 1/batch (10 Percent Determine Accuracy/Bias
Control Sample samples) differences cause of precision
(BCS3) between LCS problem
RRF and ICAL reanalyze
RRF< 20 and/or qualify
2/analytical RPD between 2 data.
sequence LCS analyses <
20
Method Blanks 1/batch No target Reclean, Accuracy/Bias-
compounds > reanalyze Contamination
QL and/or qualify
data