NYC 9/11 Public Portal Document
I
I 40 Rector Holdings, LLC
C/0 Tannenbaum Helpern Syracuse & Hirschtritt LLP
ATC Project No.; 19855-0001
October 25,2001
Ambient Air Sampling - 40 Rector Street Pagel Of?
I
M General
ATG Associates Inc. (ATC), was retained by 40 Rector Holdings LLC to provide ambient
air sampling on floors 1 through 19 in concert with a two phase building-wide cleaning
i program and to perform a general indoor air quality (lAQ) assessment of the building
following the collapse of the World Trade Center Buildings. The purpose of the ambient
air sampling was to ascertain the presence or absence of airborne asbestos, whereas,
the lAQ assessment was to determine ambient temperature, relative humidity, carbon
dioxide (COj), carbon monoxide (CO), respirable particulates and total volatile organic
compounds (TVOC) as compared to commonly accepted guidelines within the occupied
spaces of 40 Rector Street.
Ambient air sampling services were provided on September 27 - 28, 2001 upon
completion of the initial cleaning of the entire building, and between October 22 -23,
2001 upon completion of the subsequent cleaning of the entire building. lAQ services
were provided on October 1, 2001.
Per ATC proposals 15-2001-0909121, 121a, & 121b. the work performed involved the
collection of ambient air samples from representative locations on each occupied floor
and the collection of representative lAQ measurements. All ambient air samples were
collected and analyzed in accordance with the AHERA Transmission Electron Microscopy
(TEM) method as set forth at 40 CFR Part 763, Subpart E, Appendix A. ATC has selected
as a criteria for acceptable ambient air sample sets, the AHERA re-occupancy requirement
following an asbestos abatement action of an average of less than 70 asbestos structures
per square millimeter (<70 s/mm^) per sample set. All sample sets collected met the
AHERA requirement at the time of testing; this criteria is appropriate even thought the
cleaning events were not conducted as asbestos abatement projects because the AHERA
requirement is a stringent reoccupancy requirement which is designed to be protective of
children (which is a more sensitive occupancy than the expected users of the building). All
lAQ parameters measured during the lAQ assessment were within recommended
guideline ranges. However, at the time of sampling, an odor of smoke was detected in
several locations within the subject building. This odor infiltrated the building from fires at
the nearby World Trade Center site. This odor does not constitute a health hazard
although building occupants may consider the odor unpleasant and annoying. Sensitive
individuals, such as asthmatics, may find the odor irritating. As a potential remedy to the
odor, ATC provided a recommendation on October 2, 2001 for steps to minimize the odor
entrainment into the building. The recommendation suggested that the building consider
installing charcoal-impregnated filters on the HVAC system intakes to reduce aS®
entrainment; restrict to the extent possible access to the lobby via the revolving door only
which would minimize odor infiltration and limit odor movement via the elevator shafts; and
to perform daily wet-wiping and moping of the lobby with a standard cleaner or detergent
solution. As of October 23, 2001, all three recommendations have successfully been
implemented with satisfactory results in reducing aS®r entrainment into the building.
ATC Associates Inc. © 2001
CITY_21MC100__00?087975
NYC-WTC_OOO437421