Asbestos
Asbestos clearance air samples were analyzed via Transmission Electron Microscopy
(TEM) utilizing the USEPA’s PCMe method of structure counting. PCMe
TEM ambient air samples were analyzed by ATC’s New York City laboratory under
strict AHERA protocol. TEM with Energy Dispersive X-ray analysis (EDX) involves
subjecting the prepared filter media to a stream of electrons. The returning diffraction
pattern is a signature for the elemental composition of the material. This allows for
precise asbestos quantification.
Silica
A suspension of the sample particulate in tetrahydrofuran (THF) is created by dissolving
the sample filter in THF and then sonicating. The sample particulate is then deposited
onto a silver membrane filter and analyzed by X-ray diffraction giving a series of
diffraction peaks (lines) occurring at different angles relative to the sample and X-ray
source. These specific peaks are indicative of elemental silica and can be quantified.
Quality Assurance
Analysis was performed by personnel who have completed the NIOSH 582 Sampling and
Evaluating Airborne Asbestos Dust course or an equivalent course.
Personnel also participate in the NIOSH/AIHA (American Industrial Hygiene
Association) Proficiency Analytical Testing (PAT) Program to ensure consistency in
methodology. All laboratory technicians involved in air sample analysis have received
applicable EPA training.
Air Sample Results
Final air clearance samples reported concentrations of airborne fibers less than the
concentrations required by the USEPA for this project.
The clearance air sampling criteria for each of the following analytes were achieved in
accordance with project specifications.
• Asbestos in air, 0.0009 f/cc PCMe
• Fibrous glass in air, <0.01 f/cc
• Crystalline silica in air, 0.5 qg/nV
• Mercury, between 1 and 2 mg/m*
The attached appendices contain all laboratory analysis information.