WTC unoccupied building monitoring documentation, 2003

Machine-extracted title · confidence 45%

Documentation for WTC unoccupied building monitoring program, 125 Cedar Street.

NYC-WTC_000435364–000435384
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Final Report 125 Cedar Street, NYC, NY

Sample Collection

Asbestos and Fibrous Glass ATC collected asbestos and fibrous glass samples of air on 25 millimeter, mixed- cellulose ester filter membranes (0.45 & 0.8 micron pores respectively) contained in manufacturer pre-assembled, three-piece cassettes with electrically conductive, extended cowls. Pump flow rates were determined (both at the start and at the end of the sampling period and periodically by a representative of the NYCDEP) with a secondary standard (rotameter) that is calibrated quarterly against a primary standard (Gilian Instrument Corporation primary flow calibrator “Gilibrator”). Fibers from ambient air were collected with the filter cassette open-faced and positioned between three to five feet above the floor.

Silica In order to collect the desired Silica air samples for analysis, ATC performed the following tasks for air collection. A desired filter and support pad was placed into a three- piece cassette and inserted into the cyclone, which pressed firmly into the center ring of the cassette.

ATC calibrated the pump with the cyclone-cassette assembly in-line using a primary standard calibrator. The pumps, complete with cyclone-cassette assembly, were set in the breathing zone. The pump remained in their set positions for the entire sampling period. At the end of the sampling period, the cyclone/cassette assembly was removed from the holder. The cyclone was then removed from the cassette and transported to the lab for analysis.

Air Sample Analysis

Fibrous Glass PCM fibrous glass clearance samples were analyzed by ATC’s New York City laboratory utilizing the PCM method of analysis. The microscope used for sample analysis was equipped with a phase contrast condenser. Sizing and fiber counts were performed at 400X magnification. Samples were analyzed by the National Institute of Occupation Safety and Health (NIOSH) Method 7400 using method “A” counting rules. Method “A” rules count only those fibers that have a length greater than five microns and a length-to- width ratio greater than three-to-one. All air sample results are reported in fibers per cubic centimeter of air (f/cc).

ATC Project No. 15.22906.0002 Page 5

CITY_21MC100_009480771

NYC-WTC_000435371

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000435371Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000447395

WTC unoccupied building monitoring documentation for 125 Cedar Street.

Similar indexed content

Compare copies and versions →