NYC 9/11 Public Portal Document
Ambient Air Monitoring Program Section No. 16
Quality Assurance Project Plan Revision No.: 0
130 Liberty Street - NY, NY Date: August 2005
Lower Manhattan Development Corporation Page 111 of 116
• Adherence of the procedure used to the referenced methods and specific instructions,
• Correct interpretation of data (e.g., mass spectra, chromatographic interferences, etc.),
• Correctness of numerical input when computer programs are used (checked randomly) and
numerical correctness of calculations and formulas (checked randomly),
• Acceptability of QC data,
• Documentation that instruments were operating according to method specifications
(calibrations, performance checks, etc.),
• Documentation of dilution factors, standard concentrations, etc.,
• Sample holding time assessment,
• Nonconforming events have been addressed by corrective action as defined on a
nonconformance memo.
A third-level review will be performed by the Laboratory Project Manager before results are
submitted to the client. This review serves to verify the completeness of the data report and to
ensure that project requirements are met for the analyses performed. The items to be reviewed
will include:
• Results are present for every sample in the analytical batch or reporting group,
• Every parameter or target compound requested is reported,
• The correct units and correct number of significant figures are utilized,
• All nonconformances, including holding time violations, and data evaluation statements that
impact the data quality are accompanied by clearly expressed comments from the laboratory,
• The final report is legible, contains all the supporting documentation required by the project,
and is in either the standard format or in the client-required format.
A narrative to accompany the final report will be finalized by the Laboratory Project Manager.
This narrative will include relevant comments, including data anomalies and non-conformances.
16.1.3.2 Independent Review
An independent review of fixed laboratory data will be performed by TRC in order to determine
the quality of the analytical data. Data will be validated using the USEPA Contract Laboratory
Program National Functional Guidelines for Organic Data Review fEPA-540/R-99-008),
October 1999, USEPA Contract Laboratory Program National Functional Guidelines for
Inorganic Data Review (EPA 540-R-04-004), October 2004, and USEPA Contract Laboratory
Program National Functional Guidelines for Chlorinated Dioxin/Furan Data Review (EPA-540-
R-02-003), August 2002, which will be modified as necessary to include method-specific
criteria, as detailed throughout this QAPP and in the EPA and NIOSH methods.
L2005-346 Rev. 1
C ITY_D E P_WO RB Y_C AN N ATA_SU B P_000114752
NYC-WTC_000428435
OCR can misread numbers and units. Confirm readings against the page image before using them.