Part V - Quality Assurance Project Plan 133-135 Greenwich Street/21-23 Thames Street Airtek Project 05-0701 - September 29, 2005

device should be ±15 minutes. Flow Rate Transfer Standard - The flow rate transfer standard is a calibrated flow-metering device traceable to NIST standards that is used to deliver a series of discrete flow rates into the inlet of the PM2.5 sampler so that the flow-indicating device on the sampler can be accurately calibrated.

10.2.10.2 Continuous Monitoring of PM2.5 via Met One E-BAM Samplers

The monitors selected to continuously measure PM2.5 are beta-attenuation monitors manufactured by Met One Instruments, Inc. (Met One). The E-BAM monitors will be equipped with particle size selective inlets. The design of the inlets is such that particles larger than the desired size range will be removed from the air flow at the prescribed air flow rate. The units will be equipped with an inlet head to separate PM2.5. Sampling flow rate is critical to maintain the proper particle size cut points of the inlets. Flow rates are maintained at 16.7 liters per minute in the E-BAM monitors using an integral flow meter, pressure sensor, and ambient temperature sensor on board each monitor.

10.2.11 RCRA Waste Sampling

Bulk sample collection of building componants for hazard classification will include the following RCRA waste characteristic analytical procedures:

• Ignitability (RCRA waste code DOOl). American Society of Testing Materials (ASTM) method D-93-79 or D-93-80 or D-3278-78. • Corrosivity (RCRA waste code D002). Method 9045C in “Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846. NOTE: liquids may be characterized as corrosive wastes. • Reactivity (RCRA waste code D003). Analytical methods outlined in sections 7.3.3.2 or 7.3.4.2 of “Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846. • Mercury (D009) Method 7470A (aqueous samples) of “Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846 • Metals/inorganics other than mercury. Method 601 OB of “ Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846.

Building components would generally not be considered as possible RCRA characteristic wastes except for the potential that exists due to impacts by WTC dust. The notable exception to this would be surfaces painted with lead-based paint, which would typically be sampled for TCLP lead analysis. The results of RCRA characteristic analyses, as well as the material’s status as asbestos contaminated, will be used as the basis for the Waste Profile for the particular waste stream. All RCRA Characteristic results will be compared to 40 CFR 261 parts 21 through 23. In addition, the cyanide and sulfide reactivity results will be compared to SW 846 Chapter 7, Characteristics Introduction and Regulatory Definitions Interim Guidance Values.

54

CITY_DEP_WORBY_CANNATA_SUBP_000070988

NYC-WTC_000423938

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000423938Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000451195

QA plan for environmental air monitoring and waste management at NYC sites.

Similar indexed content

NYC-WTC_000424323

Plan title and approval sheet for environmental air monitoring, Greenwich/Thames.

Similar indexed content

NYC-WTC_000423504

Plan document for environmental community air monitoring at Greenwich Street and 21-23 Thames Street, Nov 2005.

Similar indexed content

NYC-WTC_000426348

Plan document outlining community air monitoring for Greenwich and Thames sites.

Similar indexed content

Compare copies and versions →