NYC 9/11 Public Portal Document
Part V - Quality Assurance Project Plan
133-135 Greenwich Street/21-23 Thames Street
Airtek Project 05-0701 - September 29, 2005
device should be ±15 minutes.
Flow Rate Transfer Standard - The flow rate transfer standard is a calibrated
flow-metering device traceable to NIST standards that is used to deliver a series
of discrete flow rates into the inlet of the PM2.5 sampler so that the flow-indicating
device on the sampler can be accurately calibrated.
10.2.10.2 Continuous Monitoring of PM2.5 via Met One E-BAM Samplers
The monitors selected to continuously measure PM2.5 are beta-attenuation monitors
manufactured by Met One Instruments, Inc. (Met One). The E-BAM monitors will be
equipped with particle size selective inlets. The design of the inlets is such that particles
larger than the desired size range will be removed from the air flow at the prescribed air
flow rate. The units will be equipped with an inlet head to separate PM2.5. Sampling flow
rate is critical to maintain the proper particle size cut points of the inlets. Flow rates are
maintained at 16.7 liters per minute in the E-BAM monitors using an integral flow meter,
pressure sensor, and ambient temperature sensor on board each monitor.
10.2.11 RCRA Waste Sampling
Bulk sample collection of building componants for hazard classification will include the
following RCRA waste characteristic analytical procedures:
• Ignitability (RCRA waste code DOOl). American Society of Testing Materials
(ASTM) method D-93-79 or D-93-80 or D-3278-78.
• Corrosivity (RCRA waste code D002). Method 9045C in “Test Methods for
Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846.
NOTE: liquids may be characterized as corrosive wastes.
• Reactivity (RCRA waste code D003). Analytical methods outlined in sections
7.3.3.2 or 7.3.4.2 of “Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods,” EPA Publication SW-846.
• Mercury (D009) Method 7470A (aqueous samples) of “Methods for Evaluating
Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846
• Metals/inorganics other than mercury. Method 601 OB of “ Methods for
Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846.
Building components would generally not be considered as possible RCRA characteristic
wastes except for the potential that exists due to impacts by WTC dust. The notable
exception to this would be surfaces painted with lead-based paint, which would typically
be sampled for TCLP lead analysis. The results of RCRA characteristic analyses, as well
as the material’s status as asbestos contaminated, will be used as the basis for the Waste
Profile for the particular waste stream. All RCRA Characteristic results will be compared
to 40 CFR 261 parts 21 through 23. In addition, the cyanide and sulfide reactivity results
will be compared to SW 846 Chapter 7, Characteristics Introduction and Regulatory
Definitions Interim Guidance Values.
54
CITY_DEP_WORBY_CANNATA_SUBP_0001 01705
NYC-WTC_000427953
OCR can misread numbers and units. Confirm readings against the page image before using them.