Indoor air quality assessment, PS 234M, Dec 2001

Machine-extracted title · confidence 30%

ATC IAQ assessment at PS 234M, BOE, December 2001.

NYC-WTC_000396309–000396312
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan December 7, 2001 Indoor Air Quality Assessment Page 2 P.S. 234 (Manhattan) ATC'Proiect No. 15-19125-0279

time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air, Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality' will be achieved at all tunes.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

TOR GANTZ ATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2)___________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NRAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature . Summer: 73-79°F at 50% RH ASHRAE55 Winter: 69-76°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile 1 ppm ' Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency NP,\AQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CITY_21MC100_002891118

NYC-WTC_000396310

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000396310Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370529

Indoor air quality measurements collected March 21, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →