NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan December 7, 2001 Indoor Air Quality Assessment Page 3 P.S. 234 (Manhattan) ATC Project No. 15-19125-0279

Table 2 shows the ranges for the lAQ parameters measured on all four days.

TABLE 2 REAL-TIME ENVIRONMENTAL MEASUREMENTS (INDOOR RANGE/OUTDOOR MAXIMUM) u 2 pee. =- ■ ' if-*'' ;>■

65.2-72.1/55.6 65.0-73.2/ 67.1 69.2 - 77.4/ 69.4 67.0-72.8/59.4

Relativmuiriidity 47.9-55.6/88.1 51.1 - 64.7/76.4 42.8-58.3/38.7 ' 37.5-54.2/47.0

& 380-500/395 394-480/430 385 -480/390 370-460/368

1-2/3 1-2/2 0-2/1 0-2/2

32 - 59/65 48-110/ 104 24-38/18 33 - 65/ 57

im) 0.0-0.9*/0.0 0.0-8.6*70.0 0.0-21.0*/0.0 0.0-2.4*/0.0

* Strong paint odor

DISCUSSION

Measurements of temperature, relative humidity, CO2, CO and respirable particulates were generally , within the guideline ranges (Table 1). The particulate (PM2.5) readings indoors reflected the conditions outdoors. Some respirable particulate readings were above the EPA standard of 65 ug/m^. This standard is a 24-hGur average and ATC collected only instantaneous real-time readings. Elevated TVOC readings resulted directly from painting activity in the building on the days the readings were made. The odor had dissipated considerably by the last day of measurements.

It must be noted that all of these measurements were made in an unoccupied building. Only ATC personnel and custodial staff were present. Levels would be expected to be different in a fully occupied building. Temperature, relative humidity, CO2 and respirable particulates may all be expected to increase to varying degrees when the school is occupied.

CITY_21MC100_002891119

NYC-WTC_000396311

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000396311Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370529

Indoor air quality measurements collected March 21, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →