Mr. Bernard P. Orlan December 7, 2001
Indoor Air Quality Assessment Page 3
P.S. 234 (Manhattan) ATC Project No. 15-19125-0279
Table 2 shows the ranges for the lAQ parameters measured on all four days.
TABLE 2
REAL-TIME ENVIRONMENTAL MEASUREMENTS
(INDOOR RANGE'OUTDOOR MAXIMUM)
miete. -W I I'M5Y30i ®ec.:2.
? .t. 'L.. .x f
iatuna
65.2-72.1/55.6 65.0-73.2/ 67.1 69.2 - 77.4/ 69.4 67.0-72.8/59.4
n
47.9-55.6/88.1 51.1 - 64.7/76.4 42.8-58.3/38.7 37.5-54.2/ 47.0
m
380-500/395 394-480/430 385 -480/390 370-460/368
1-2/3 1-2/2 0-2/1 0-2/2
32 - 59/65 48-110/104 24-38/18 33 -65/ 57
TWCsBI
0.0-0.9*/0.0 0.0-8.6*/ 0.0 0.0-21.0*/0.0 .0.0-2.4*/0.0
* Strong paint odor
DISCUSSION
Measurements of temperature, relative humidity, CO2, CO and respirable particulates were
generally within the guideline ranges (Table 1). The particulate (PM2.5) readings indoors
reflected the conditions outdoors. Some respirable particulate readings were above the EPA
standard of 65 ug/mY This standard is a 24-hour average and ATC collected only instantaneous
real-time readings. Elevated TVOC readings resulted directly from painting activity in the
building on the days the readings were made. The odor had dissipated considerably by the last
day of measurements.
It must be noted that all of these measurements were made m an unoccupied building. Only
ATC personnel and custodial staff were present. Levels would be expected to be different in a
fully occupied building. Temperature, relative humidity, CO2 and respirable particulates may
all be expected to increase to varying degrees when the school is occupied.