Mr. Bernard P. Orlan December 12, 2001
Air Sampling for Hydrocarbons & Metals Page 2
P. S. 234CManhattan') ATC Project No. 15-19125-0279
The established regulatory values for HCs and metals are intended for industrial workplace
exposures and are not generally applicable to office/school settings. There are no standards for
hydrocarbon vapors or metals for indoor air in hon-industrial situations.
HYDROCARBON RESULTS
Each sample was analyzed for the following sixteen hydrocarbon (HC) compounds: Pentane,
Acetone, Methylene chloride. Hexane, Chloroform, Methyl chloroform. Total Other A
Hydrocarbons, Benzene, 1, 2-Dichloroethane, Trichloroethylene, Toluene, Perchloroethylene
(tetrachloroethylene). Chlorobenzene, Ethylbenzene, Styrene, Cumene (isopropylbenzene).
Xylenes, Total Other B Hydrocarbons. The limit of detection for each compound was 0.020
milligrams per sample. The airborne concentrations were calculated by dividing the amount
found in the sarnple by the volume of air collected and converting the quotient to parts per million
(ppm).
The HC present above the limits of detection were the Total Other B Hydrocarbons which were
found in all three indoor samples collected on November 29* (range: 0.095 - 0.322 ppm) and
30* (range: 0.780 - 5.00 ppm). In one sample collected on November 30*, tetrachloroethylene
(0.036 ppm), ethylbenzene (0.061 ppm) and xylenes (0.294 ppm) were detected. In one sample
collected on December 1®, contained tetrachloroethylene(0.346 ppm), chlorobenzene (0.129
ppm), ethylbenzene (0.154 ppm), styrene (0.076 ppm), xylene (0.859 ppm) and total other B
hydrocarbons (16.6 ppm). (As stated previously, total B hydrocarbons include petroleum
naphtha and mineral spirits which are common components of paint). These levels corresponded
with the highest real-time TVOC readings. Xylenes and other B hydrocarbons were also detected
in the two other indoor samples from that date. These compounds were not detected in the roof
sample. The custodial staff was painting in various areas inside the school during the sampling
period and a strong paint odor was detected by ATC. Real-time measurements for total volatile
organic compounds made during the same time period were as high as 21 ppm (Dec. 1). Only
total other B hydrocarbons were detected (0.158-0.301 ppm) in the indoor samples from
December 2"“’. The paint odor had dissipated substantially on that date.
METAL SAMPLE RESULTS
Each sample was analyzed for aluminum, cadmium, chromium, cobalt, copper, iron, magnesium,
manganese, molybdenum, nickel and zinc. The limits of detection ranged from less than 0.0001
milligrams per sample (mg/sample) for nickel, copper, cobalt and cadmium to 0.001 mg/sample
for iron and molybdenum. The airborne concentrations were calculated by dividing the amount
found in the sample by the volume of air collected.
Chromium were detected in all samples however it was detected in the blanks from both days.
When the chromium level in the blank is subtracted from the amount in the samples, the airborne
concentrations drop below the limit of detection. Any chromium detected was already in" the
filter and did not come from the ambient air. On November 29*, trace amounts of iron and
copper were found in the roof sample only. Iron was found in one indoor sample (0.001 mg/m^)
and in the outdoor sample (0.002 mg/m^) on November 30* and outdoors (0.001 mg/m") on
December 2”^. Aluminum was detected in two indoor samples and the outdoor sample from
December 2"‘‘, however as was the case with chromium, the same amount was found in the blank.
The actual airborne concentration was below the limit of detection.