Ambient air protocol, PS 150 Manhattan

Machine-extracted title · confidence 60%

Ambient air and dust sampling protocol for PS 150 Manhattan after WTC events.

NYC-WTC_000385841–000385848
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

AMBIENT AIR AND DUST SAMPLING PROTOCOL for PSI SOM Page 2 of 8

1 In the event that any one sample result exceed 70 s/mm^ ATC shall immediately notify BOE representative Mr. Mohamed Hemida, the UFT and the PA consultant. BOE shall notify the school principal, the school custodian and the plant manager. The said parties will assess the situation and implement the appropriate response action(s) immediately.

INDOOR AIR QUAUTY

To address lAQ concerns, each day from Monday through Friday, the following shail be performed;

• A visual inspection to assess conditions present in the school at the time of the site visit.

• Collect approximately 40 real-time environmental measurements of temperature (T)

Collect approximately 40 real-time environmental measurements of relative humidity (RH)

• Collect approximately 40 real-time environmental measurements of carbon dioxide (CO2)

• Collect approximately 40 real-time environmental measurements of carbon monoxide (CO)

• Collect approximately 40 real-time environmental measurements of total volatile organic compounds (TVOCs)

Collect approximately 40 real-time environmental measurements of respirable particulates (PM2.5).

EVALUA TIONCRITERIA:

Since, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools at this time, for the real-time data collected, the commonly accepted guidelines cited in the following publications and table below shall be utilized:

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy fASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

CITY_21MC100_009214724

NYC-WTC_000385842

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385842Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →