AMBIENT AIR AND DUST SAMPLING PROTOCOL for PSI SOM Page 2 of 8
f In the event that any one sample result exceed 70 s/mm^ ATC shall immediately notify BOE representative Mr. Mohamed Hemida, the LIFT and the PA consultant BOE shall notify the school principal, the school custodian and the plant manager. The said parties will assess the situation and implement the appropriate response action(s) immediately.
INDOOR AIR QUALITY
To address lAQ concerns, each day from Monday through Friday, the following shall be performed: •
• A visual inspection to assess conditions present in the school at the time of the site visit.
• Collect approximately 40 real-time environmental measurements of temperature (T)
Collect approximately 40 real-time environmental measurements of relative humidity (RH)
• Collect approximately 40 real-time environmental measurements of carbon dioxide (CO2)
• Collect approximately 40 real-time environmental measurements of carbon monoxide (CO)
• Collect approximately 40 real-time environmental measurements of total volatile organic compounds (TVOCs)
• Collect approximately 40 real-time environmental measurements of respirable particulates (PM2.5).
EVALUATION CRITERIA:
Since, there are no regulatory standards for indoor air quality in non-industriai buildings, such as offices and schools at this time, for the real-time data collected, the commonly accepted guidelines cited in the following publications and table below shall be utilized:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industnal Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
I
CITY_21MC100_003267229
NYC-WTC_000324186
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000324143
Ambient air and dust sampling protocol for PS 150 in Manhattan.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324159
Ambient air/dust protocol for PS 234 Manhattan; asbestos IAQ.
16 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324176
Ambient air and dust sampling protocol for PS 89 Manhattan, asbestos monitoring.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324211
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324203
Ambient air and dust sampling protocol for PS 234; asbestos-monitoring.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000200230
Draft protocol document establishing daily ambient air and dust sampling procedures for asbestos monitoring at P.S./I.S. 89 Manhattan.
15 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385841
Ambient air and dust sampling protocol for PS 150 Manhattan after WTC events.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385851
Draft ambient air sampling protocol for PS 150 Manhattan with lAQ considerations.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385819
Lab protocol outlining ambient air and dust sampling for asbestos at IS 89 Manhattan.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385797
Ambient air/dust sampling protocol for IS 89 after WTC cleanup.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385777
Protocol for ambient air and dust sampling around PS 234 post-WTC cleanup.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385808
Protocol detailing daily ambient air sampling inside the IS 89 building.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000324143
Ambient air and dust sampling protocol for PS 150 in Manhattan.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385841
Ambient air and dust sampling protocol for PS 150 Manhattan after WTC events.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385851
Draft ambient air sampling protocol for PS 150 Manhattan with lAQ considerations.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324203
Ambient air and dust sampling protocol for PS 234; asbestos-monitoring.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385787
Ambient air sampling protocol for PS 234 with daily inside/outside tests.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385777
Protocol for ambient air and dust sampling around PS 234 post-WTC cleanup.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000324143
Ambient air and dust sampling protocol for PS 150 in Manhattan.
Similar indexed content
NYC-WTC_000385841
Ambient air and dust sampling protocol for PS 150 Manhattan after WTC events.
Similar indexed content
NYC-WTC_000385851
Draft ambient air sampling protocol for PS 150 Manhattan with lAQ considerations.
Similar indexed content
NYC-WTC_000324159
Ambient air/dust protocol for PS 234 Manhattan; asbestos IAQ.
Similar indexed content
NYC-WTC_000324176
Ambient air and dust sampling protocol for PS 89 Manhattan, asbestos monitoring.
Similar indexed content